Emerson 250-400kVA manual OK to Transfer, Load on bypass, UPS available

Page 26

Operation

2.3.2OK to Transfer

The OK to Transfer status message will be displayed when the bypass line and UPS output power are both available, their voltage, frequency and phase synchronization are matched within specifications, and the Static Switch Disconnects are closed (ON). An alarm message may be displayed to indicate Load On Bypass (Figure 24). If no alarm is displayed, the operating status is Load On UPS (Figure 25).

When the OK to Transfer message is displayed, the load can be manually transferred from the UPS to bypass or the load can be manually retransferred from the bypass to the UPS.

To perform a manual transfer, Use the Load Transfer Procedures screen. Refer to 2.4.2 - Load Transfer Procedures.

The UPS control logic will initiate an automatic transfer to bypass if an overload condition exceeds the system current versus time window or if a UPS fault is detected. The control logic may initiate an automatic retransfer to the UPS system when the system is recovering from overloads lasting less than five minutes. Refer to 2.6 - Automatic Operations.

Figure 24 Load on bypass, UPS available

Bypass

BFB

Input

DC Bus

CB1

CB2

Battery

 

System

MBD

Figure 25 Load on UPS, bypass available

Bypass

BFB

Module Output

Input

CB1

Battery

System

DC Bus

CB2

MBD

Module Output

20

Image 26
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions Modes of Operation Normal ModeGeneral Description Maintenance Bypass Bypass ModeBattery Mode OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Startup Menu Event ManagementStatus Reports Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Help ResetMetering SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Re-Transfer Procedure Load Transfer ProceduresTransfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass System Shutdown Procedure Shutdown ProceduresUPS Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersLimited Life Components Battery MaintenanceUPS component service life Component Expected Life ReplaceBattery Safety Precautions Battery retorque values Matching Battery Cabinets-OptionalBattery voltage, nominal and float Rack-Mounted Batteries Torque specifications, unless otherwise labeledDetecting Trouble Torque RequirementsCorrective Actions Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Parameter Specification Battery OperationEnvironmental specifications Environmental ConditionsLiebert NXL Model Size 250 Electrical specificationsBattery & DC Parameters Input ParametersPhysical Parameters & Standards, in mm Liebert NXL Model SizeSystem Parameter Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ti n Ne tIti That