Emerson 250-400kVA manual Startup Procedure

Page 30

Operation

2.4.1 Startup Procedure

! CAUTION

The following procedure provides power to the critical load distribution system. Verify that the critical load distribution is ready to accept power. Make sure that personnel and equipment are ready for the critical load distribution system to be energized.

If your installation includes a Maintenance Bypass, you may already be supplying power to the criti- cal load equipment through the Maintenance Bypass. If there is no power to the critical load, apply power through the UPS bypass line per the following procedure.

During startup, power is supplied to the critical load through the UPS (internal) bypass line while the UPS system is being energized. Depending on the reason for the UPS system shutdown, power may be present in the bypass line. To determine this, check the Monitor/Mimic Display screen after control power is available.

1.Before you apply power to the UPS modules, determine the position of the following circuit breakers and switches:

Input Circuit Breaker (CB1)—Verify that this breaker on the front of the UPS cabinet (Figure 2) is in the Open position.

Module Battery Disconnect (MBD)—Verify that this external breaker is open or tripped. If battery cabinets are used, verify that breakers on all the cabinets are open.

Bypass Circuit Breaker (BFB)—This circuit breaker (Figure 2) should be open.

NOTE

Power to the critical load may already be supplied through this breaker.

• Output Circuit Breaker (CB2)—This motorized circuit breaker (Figure 2) should be open.

NOTE

If the system was shut down in response to an “Emergency Off”, there may be alarm messages on the touchscreen that describe system conditions before (or at the time of) the shutdown. Some or all of the alarm conditions may have been resolved. To clear these alarm messages, turn off control power (see Figure 2). Wait at least 10 minutes for the control power circuitry to completely de-energize. After 10 minutes, turn control power back on and wait two minutes before continuing.

! WARNING

Risk of electrical shock and high short circuit current. Can cause equipment damage, personal injury and death.

If the UPS has been shut down for maintenance, verify that all of the UPS system doors are closed and latched. All test equipment must be removed from the system. All electrical connections must be secure.

2.Power must be provided to the UPS controls so the operator can use the display touchscreen and so the system logic can function properly. The display touchscreen may be used to monitor UPS system status, even when the UPS modules are not operating. This will be the usual condition unless you are recovering from a maintenance shutdown.

3.If the bypass line is not supplying the load, energize the bypass line by:

a.Closing the Bypass Input Breaker (BIB), external to the UPS. This breaker may be in the Maintenance Bypass Cabinet.

The display touchscreen should start up.

b.Pressing the “Start-Up” then “Manual Start” menu buttons (see Figure 30).

c.The “Close BFB” message appears in the multipurpose window. Close the BFB breaker (see Figure 2).

d.A “Press OK to issue BPSS On Command” message appears. Press OK to continue. This will energize the load on the UPS internal bypass.

24

Image 30
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions Normal Mode General DescriptionModes of Operation Maintenance Bypass Bypass ModeBattery Mode OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Event Management Status Reports MenuStartup Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Help ResetMetering SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Re-Transfer Procedure Load Transfer ProceduresTransfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass System Shutdown Procedure Shutdown ProceduresUPS Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersLimited Life Components Battery MaintenanceUPS component service life Component Expected Life ReplaceBattery Safety Precautions Matching Battery Cabinets-Optional Battery voltage, nominal and floatBattery retorque values Rack-Mounted Batteries Torque specifications, unless otherwise labeledDetecting Trouble Torque RequirementsReporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Parameter Specification Battery OperationEnvironmental specifications Environmental ConditionsLiebert NXL Model Size 250 Electrical specificationsBattery & DC Parameters Input ParametersLiebert NXL Model Size System ParameterPhysical Parameters & Standards, in mm Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ti n Ne tIti That