| UPS Alarm and Status Messages | |
|
|
|
| |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
| This is a summary event that informs the user that | Press “SILENCE” to silence the audible alarm. | |
|
| a circuit breaker that was either signaled to close | Check the | |
|
| Window to determine which breaker or switch is | ||
|
| or was manually closed failed to report a closed | ||
|
| open. | ||
Breaker Close Fail | status. | |||
If the open breaker cannot be reset or closed, or if | ||||
|
| The Breaker Close Fail event indicates a | ||
|
| all breakers are closed but the | ||
|
| mismatch between the expected state of a | ||
|
| does not agree, or the alarm cannot be cleared, | ||
|
| breaker and the reported state of the breaker. | ||
|
| contact your | ||
|
|
| ||
|
|
|
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
| This is a summary event that informs the user a | Check the | |
|
| Window to determine which breaker or switch that | ||
|
| circuit breaker that was either signaled to open or | ||
|
| should be open is still closed. | ||
|
| was manually opened failed to report an open | If a breaker that should be open shows closed, or if | |
Breaker Open Fail | status. | |||
the breaker in question actually is open but the fault | ||||
|
| The Breaker Open Fail event indicates a | ||
|
| is still present, attempt to clear the fault by pressing | ||
|
| mismatch between the expected state of a | ||
|
| “RESET.” | ||
|
| breaker and the reported state of the breaker. | ||
|
| If the event does not reset, contact your factory- | ||
|
|
| ||
|
|
| authorized service provider. | |
|
|
|
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Observe the calculated load percentage on A phase | |
|
|
| displayed on the Module Output Meter. If the A | |
|
| The critical load is greater than 110% while the | phase steady state load percentage exceeds 110%, | |
|
| perform the following: | ||
|
| UPS is on bypass. The controls may shut the unit | ||
|
| If Maintenance Bypass is available, follow Standard | ||
|
| down if the overload condition does not clear | Operating Procedures to transfer the load to | |
|
| within the allotted time. Allotted time is variable, | ||
|
| Maintenance Bypass. | ||
|
| and is inversely proportional to the amplitude of | ||
Byp Overload | If Maintenance Bypass is not available but the | |||
the overload, i.e., the greater the amplitude of the | ||||
Ph A |
| system has an Internal Bypass Breaker (CB3 on the | ||
|
| overload, the less time the unit continues to | ||
|
| support the load. | ||
|
| on the severity of the overload, the possibility exists | ||
|
| This alarm is | ||
|
| that CB3 could trip if the overload exceeds the | ||
|
| no longer present, the alarm and any control | ||
|
| breaker rating. | ||
|
| activity tied to the alarm reverts to normal. | ||
|
| Investigate the overload condition. | ||
|
|
| ||
|
|
| If the Module Output Meter does not indicate an | |
|
|
| overload condition, perform the previous steps and | |
|
|
| contact your | |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Observe the calculated load percentage on B phase | |
|
|
| displayed on the Module Output Meter. If the B | |
|
| The critical load is greater than 110% while the | phase steady state load percentage exceeds 110%, | |
|
| perform the following: | ||
|
| UPS is on bypass. The controls may shut the unit | ||
|
| down if the overload condition does not clear | If Maintenance Bypass is available, follow Standard | |
|
| Operating Procedures to transfer the load to | ||
|
| within the allotted time. Allotted time is variable, | ||
|
| Maintenance Bypass. | ||
|
| and is inversely proportional to the amplitude of | ||
Byp Overload | If Maintenance Bypass is not available but the | |||
the overload, i.e., the greater the amplitude of the | ||||
Ph B |
| system has an Internal Bypass Breaker (CB3 on the | ||
|
| overload, the less time the unit continues to | ||
|
| support the load. | ||
|
| on the severity of the overload, the possibility exists | ||
|
| This alarm is | ||
|
| that CB3 could trip if the overload exceeds the | ||
|
| no longer present, the alarm and any control | ||
|
| breaker rating. | ||
|
| activity tied to the alarm reverts to normal | ||
|
| Investigate the overload condition. | ||
|
|
| ||
|
|
| If the Module Output Meter does not indicate an | |
|
|
| overload condition, perform the previous steps and | |
|
|
| contact your |