Emerson 250-400kVA manual If the command to terminate Regeneration Mode

Page 67

 

 

 

UPS Alarm and Status Messages

 

 

 

 

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

Regeneration Mode is a service mode that is

 

 

 

normally controlled by the service technician.

Under normal circumstances, none.

 

 

Regeneration Mode Status or Alarm messages

 

 

If this message is active, and there is no clear

 

 

are generally intended for the service person.

 

 

reason why the UPS was in Regeneration Mode, or

Regen Terminated

This status message informs the user that Regen

if the command to terminate Regeneration Mode

 

 

Mode is no longer active.

was not issued, contact your factory-authorized

 

 

This status message is self-clearing. When the

 

 

service provider.

 

 

condition is no longer present, the alarm and any

 

 

 

 

 

control activity tied to the alarm reverts to normal.

 

 

 

 

 

 

 

The Static Bypass Switch (BPSS) was turned off

 

 

 

by an external signal.

 

 

 

This indicates an external signal forcing the BPSS

 

 

 

to remain off is active.

Check the state of the Remote Off BPSS signal.

 

 

This type of signal is wired into an Input Contact

 

 

If this signal is not active, or if no signal wires are

Remote Off BPSS

Isolator and the specific channel is assigned as

present, contact your factory-authorized service

 

 

Remote Off BPSS.

 

 

provider.

 

 

This status message is self-clearing. When the

 

 

 

 

 

condition is no longer present, the message and

 

 

 

any control activity tied to the status event reverts

 

 

 

to normal.

 

 

 

The Inverter was turned off by an external signal.

 

 

 

This indicates an external signal forcing the

 

 

 

Inverter to remain off is active.

Check the state of the Remote Off Inverter signal.

 

 

This type of signal is wired into an Input Contact

Remote Off Inv

Isolator and the specific channel is assigned as

If this signal is not active, or if no signal wires are

Remote Off Inverter.

present, contact your factory-authorized service

 

 

 

 

This status message is self-clearing. When the

provider.

 

 

condition is no longer present, the message and

 

 

 

any control activity tied to the status event reverts

 

 

 

to normal.

 

 

 

The Rectifier was turned off by an external signal.

 

 

 

This indicates an external signal forcing the

 

 

 

Rectifier to remain off is active.

Check the state of the Remote Off Rectifier signal.

 

 

This type of signal is wired into an Input Contact

Remote Off Rect

Isolator and the specific channel is assigned as

If this signal is not active, or if no signal wires are

Remote Off Rectifier.

present, contact your factory-authorized service

 

 

 

 

This status message is self-clearing. When the

provider.

 

 

condition is no longer present, the message and

 

 

 

any control activity tied to the status event reverts

 

 

 

to normal.

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Resolve the issue that precipitated the REPO.

 

 

 

For safety, the UPS latches an REPO event. There

 

 

 

are two ways to clear the latch:

 

 

 

1. Press the Reset pushbutton on the External

 

 

The UPS shuts down in response to an active

Interface Board (EIB).

 

 

2. From HMI front panel display, press OK button

REPO Shutdown

Remote Emergency Power Off (REPO)

when ” Press OK to Reset EPO Latched signal”

 

 

command.

 

 

message is displayed

 

 

 

 

 

 

in a dialog box.

 

 

 

Verify the REPO is cleared by observing the REPO

 

 

 

alarm in the Active Event Window is gone.

 

 

 

Restart the UPS by pressing “Startup,” “Manual

 

 

 

Start,” and follow the prompts.

 

 

Automatic Restart is in progress. This message

To complete the Automatic Restart, follow the

Restart in Process

clears when the Automatic Restart sequence is

prompts on the display.

 

 

complete.

 

 

 

 

 

 

 

 

 

Automatic Restart of the UPS is not allowed

Investigate and resolve the external signal forcing

Restart Inhibited

because of an external signal.

the UPS to remain off.

Automatic Restart Inhibit is active when signaled

If you do not have an ICI, or if there are no external

 

 

from an external source. The signal is wired into

off signals input to the UPS, contact your factory-

 

 

Input Contact Interface (ICI 1).

authorized service provider.

61

Image 67
Contents Liebert NXL Contacting Liebert for Support Battery Cabinet PrecautionsTable of Contents Specifications Figures Page Important Safety Instructions General Description Normal ModeModes of Operation Options Bypass ModeBattery Mode Maintenance BypassIntroduction Main component locations FeaturesMimic display Monitor/mimic display example Utility fail Monitor/mimic display example Normal power flowMonitor/mimic display example Load on bypass, UPS On Menu tree Touchscreen Navigation Main Display ScreenRating Parameters Configurations Menu RatingSystem Settings parameters User SettingsAdjustable setpoints parameters Adjustable SetpointsCell Count Adjustment Status Reports Menu Event ManagementStartup Menu Shutdown menu Shutdown MenuTransfer Menu Transfer/retransfer commandsTime remaining display Battery Management MenuDisplay summary see Figure Silence ResetMetering HelpLoad on bypass, UPS available OK to TransferInput power fail, load on battery Input Power Failure-Load on BatteryEmergency Module Off Off BatteryRemote Emergency Power Off Manual ProceduresStartup Procedure Startup commands Maintenance Bypass Load Transfers Load Transfer ProceduresTransfer Procedure Re-Transfer ProcedureMaintenance Bypass Load Transfers-If Load is on UPS Bypass Automatic Operations Shutdown ProceduresUPS Shutdown Procedure System Shutdown ProcedureCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Automatic Transfers to Bypass, UPS System FaultsSafety Precautions Routine Maintenance Liebert ServicesAir Filters Record LogComponent Expected Life Replace Battery MaintenanceUPS component service life Limited Life ComponentsBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery retorque values Torque Requirements Torque specifications, unless otherwise labeledDetecting Trouble Rack-Mounted BatteriesUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Environmental Conditions Battery OperationEnvironmental specifications Parameter SpecificationInput Parameters Electrical specificationsBattery & DC Parameters Liebert NXL Model Size 250System Parameter Liebert NXL Model SizePhysical Parameters & Standards, in mm Specifications Event Message Event Definition Recommended Action Liebert NXL alarm and status messagesObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page That Ne tIti Ti n