| UPS Alarm and Status Messages | |
|
|
|
| |
Table 7 | Liebert NXL alarm and status messages (continued) | |||
|
|
| ||
Event Message | Event Definition | Recommended Action | ||
|
| Regeneration Mode is a service mode that is |
| |
|
| normally controlled by the service technician. | Under normal circumstances, none. | |
|
| Regeneration Mode Status or Alarm messages | ||
|
| If this message is active, and there is no clear | ||
|
| are generally intended for the service person. | ||
|
| reason why the UPS was in Regeneration Mode, or | ||
Regen Terminated | This status message informs the user that Regen | |||
if the command to terminate Regeneration Mode | ||||
|
| Mode is no longer active. | was not issued, contact your | |
|
| This status message is | ||
|
| service provider. | ||
|
| condition is no longer present, the alarm and any | ||
|
|
| ||
|
| control activity tied to the alarm reverts to normal. |
| |
|
|
|
| |
|
| The Static Bypass Switch (BPSS) was turned off |
| |
|
| by an external signal. |
| |
|
| This indicates an external signal forcing the BPSS |
| |
|
| to remain off is active. | Check the state of the Remote Off BPSS signal. | |
|
| This type of signal is wired into an Input Contact | ||
|
| If this signal is not active, or if no signal wires are | ||
Remote Off BPSS | Isolator and the specific channel is assigned as | |||
present, contact your | ||||
|
| Remote Off BPSS. | ||
|
| provider. | ||
|
| This status message is | ||
|
|
| ||
|
| condition is no longer present, the message and |
| |
|
| any control activity tied to the status event reverts |
| |
|
| to normal. |
| |
|
| The Inverter was turned off by an external signal. |
| |
|
| This indicates an external signal forcing the |
| |
|
| Inverter to remain off is active. | Check the state of the Remote Off Inverter signal. | |
|
| This type of signal is wired into an Input Contact | ||
Remote Off Inv | Isolator and the specific channel is assigned as | If this signal is not active, or if no signal wires are | ||
Remote Off Inverter. | present, contact your | |||
|
| |||
|
| This status message is | provider. | |
|
| condition is no longer present, the message and |
| |
|
| any control activity tied to the status event reverts |
| |
|
| to normal. |
| |
|
| The Rectifier was turned off by an external signal. |
| |
|
| This indicates an external signal forcing the |
| |
|
| Rectifier to remain off is active. | Check the state of the Remote Off Rectifier signal. | |
|
| This type of signal is wired into an Input Contact | ||
Remote Off Rect | Isolator and the specific channel is assigned as | If this signal is not active, or if no signal wires are | ||
Remote Off Rectifier. | present, contact your | |||
|
| |||
|
| This status message is | provider. | |
|
| condition is no longer present, the message and |
| |
|
| any control activity tied to the status event reverts |
| |
|
| to normal. |
| |
|
|
| Press “SILENCE” to silence the audible alarm. | |
|
|
| Resolve the issue that precipitated the REPO. | |
|
|
| For safety, the UPS latches an REPO event. There | |
|
|
| are two ways to clear the latch: | |
|
|
| 1. Press the Reset pushbutton on the External | |
|
| The UPS shuts down in response to an active | Interface Board (EIB). | |
|
| 2. From HMI front panel display, press OK button | ||
REPO Shutdown | Remote Emergency Power Off (REPO) | |||
when ” Press OK to Reset EPO Latched signal” | ||||
|
| command. | ||
|
| message is displayed | ||
|
|
| ||
|
|
| in a dialog box. | |
|
|
| Verify the REPO is cleared by observing the REPO | |
|
|
| alarm in the Active Event Window is gone. | |
|
|
| Restart the UPS by pressing “Startup,” “Manual | |
|
|
| Start,” and follow the prompts. | |
|
| Automatic Restart is in progress. This message | To complete the Automatic Restart, follow the | |
Restart in Process | clears when the Automatic Restart sequence is | |||
prompts on the display. | ||||
|
| complete. | ||
|
|
| ||
|
|
|
| |
|
| Automatic Restart of the UPS is not allowed | Investigate and resolve the external signal forcing | |
Restart Inhibited | because of an external signal. | the UPS to remain off. | ||
Automatic Restart Inhibit is active when signaled | If you do not have an ICI, or if there are no external | |||
|
| from an external source. The signal is wired into | off signals input to the UPS, contact your factory- | |
|
| Input Contact Interface (ICI 1). | authorized service provider. |