Emerson 250-400kVA manual Safety Precautions

Page 37

Maintenance

3.0MAINTENANCE

3.1Safety Precautions

Observe the safety precautions in Battery Cabinet Precautions inside the front cover.

NOTE

Service and maintenance work must be performed only by properly trained and qualified personnel and in accordance with applicable regulations as well as with manufacturers’ specifications.

Observe ALL of the WARNINGS below before performing ANY maintenance on the UPS System and associated equipment. Also observe the manufacturer’s safety precautions pertaining to the battery, along with the battery safety precautions in this section.

! WARNING

Risk of electrical shock and high short circuit current. Can cause equipment damage, personal injury and death.

Extreme caution is required when performing maintenance.

Be constantly aware that the UPS system contains high DC as well as AC voltages. With input power off and the battery disconnected, high voltage at filter capacitors and power circuits should be discharged within 30 seconds. However, if a power circuit failure has occurred, you should assume that high voltage may still exist after shutdown. Check with a voltmeter before making contact.

AC voltage will remain on the bypass and output circuit breakers and the static bypass switch, unless associated external circuit breakers are opened.

Check for voltage with both AC and DC voltmeters prior to making contact.

When the UPS system is under power, both the operator and any test equipment must be isolated from direct contact with earth ground and the UPS chassis frame by using rubber mats.

Some components within the cabinets are not connected to chassis ground.

Any contact between floating circuits and the chassis is a lethal shock hazard. Use differential oscilloscopes when measuring a floating circuit.

Exercise caution that the test instrument exterior does not make contact, either physically or electrically, with earth ground.

In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or others approved for use in fighting electrical fires.

! WARNING

Risk of electrical shock and high short circuit current. Can cause equipment damage, personal injury and death.

Always identify connecting wiring prior to disconnecting any wiring. Do not substitute parts except as authorized by Liebert Corporation.

Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings, etc.

Contact Liebert Services if you are not sure of the procedures to follow or if you are not familiar with the circuitry.

31

Image 37
Contents Liebert NXL Contacting Liebert for Support Battery Cabinet PrecautionsTable of Contents Specifications Figures Page Important Safety Instructions General Description Normal ModeModes of Operation Battery Mode Bypass ModeMaintenance Bypass OptionsIntroduction Main component locations FeaturesMimic display Monitor/mimic display example Utility fail Monitor/mimic display example Normal power flowMonitor/mimic display example Load on bypass, UPS On Menu tree Touchscreen Navigation Main Display ScreenRating Parameters Configurations Menu RatingSystem Settings parameters User SettingsAdjustable setpoints parameters Adjustable SetpointsCell Count Adjustment Status Reports Menu Event ManagementStartup Menu Shutdown menu Shutdown MenuTransfer Menu Transfer/retransfer commandsTime remaining display Battery Management MenuDisplay summary see Figure Metering ResetHelp SilenceLoad on bypass, UPS available OK to TransferInput power fail, load on battery Input Power Failure-Load on BatteryEmergency Module Off Off BatteryRemote Emergency Power Off Manual ProceduresStartup Procedure Startup commands Transfer Procedure Load Transfer ProceduresRe-Transfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass UPS Shutdown Procedure Shutdown ProceduresSystem Shutdown Procedure Automatic OperationsCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Automatic Transfers to Bypass, UPS System FaultsSafety Precautions Routine Maintenance Liebert ServicesAir Filters Record LogUPS component service life Battery MaintenanceLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery retorque values Detecting Trouble Torque specifications, unless otherwise labeledRack-Mounted Batteries Torque RequirementsUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Environmental specifications Battery OperationParameter Specification Environmental ConditionsBattery & DC Parameters Electrical specificationsLiebert NXL Model Size 250 Input ParametersSystem Parameter Liebert NXL Model SizePhysical Parameters & Standards, in mm Specifications Event Message Event Definition Recommended Action Liebert NXL alarm and status messagesObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Iti Ne tTi n That