Emerson 250-400kVA manual Off Battery, Emergency Module Off

Page 28

Operation

2.3.4Off Battery

The battery plant can be disconnected from the UPS, if required for battery maintenance, by opening the module battery disconnect (MBD) circuit breaker. In this situation the UPS module will continue to supply conditioned power to the critical load, but if input power fails the UPS system cannot supply power to the load.

! CAUTION

When the UPS system is operating with the module battery disconnect (MBD) circuit breaker(s) open, the critical load is not protected from loss of the utility source power.

Figure 27 Load on UPS, battery not available

Bypass

BFB

Input

DC Bus

 

CB1

CB2

Module Output

Battery System

MBD

2.3.5Emergency Module Off

The Local Emergency Module Off (LEMO) mode will transfer the critical load to the bypass line and remove power from all UPS module components except the controls, bypass circuit breaker and the static switch.

The Emergency Module Off control is a guarded pad next to the display touchscreen (Figure 2).

Lift the cover and press the pad. The load will be transferred to bypass, and the battery (MBD), input and output circuit breakers will be opened (tripped). Refer to 2.5 - Shutdown Procedures.

Figure 28 Emergency modules off

Bypass

BFB

Input

CB1

DC Bus

CB2

Module Output

Battery System

MBD

22

Image 28
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions General Description Normal ModeModes of Operation Bypass Mode Battery ModeMaintenance Bypass OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Status Reports Menu Event ManagementStartup Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Reset MeteringHelp SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Load Transfer Procedures Transfer ProcedureRe-Transfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass Shutdown Procedures UPS Shutdown ProcedureSystem Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersBattery Maintenance UPS component service lifeLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery retorque values Torque specifications, unless otherwise labeled Detecting TroubleRack-Mounted Batteries Torque RequirementsUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Battery Operation Environmental specificationsParameter Specification Environmental ConditionsElectrical specifications Battery & DC ParametersLiebert NXL Model Size 250 Input ParametersSystem Parameter Liebert NXL Model SizePhysical Parameters & Standards, in mm Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ne t ItiTi n That