Emerson 250-400kVA When manual transfers are enabled

Page 64

 

 

 

UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

 

The condition clears from the Active Event Window

 

 

 

when manual transfers are enabled.

 

 

 

A possible reason for this condition is an unstable

 

 

This summary event means the conditions

generator. If the generator frequency is not stable,

 

 

or not at 60 Hz, the Inverter may have difficulty

 

 

required to perform a manual transfer to bypass

 

 

maintaining synchronization with the bypass

 

 

are not met (Inverter must be in sync with

 

 

source.

 

 

bypass).

Manual Xfer Inhibit

To check the synchronization of the Inverter to

 

 

This status message is self-clearing. When the

bypass, click “Transfer” and observe the

 

 

condition is no longer present, the message and

 

 

synchroscope. A non-sync condition is indicated by

 

 

any control activity tied to the status event reverts

 

 

a varying phase angle error, rather than a stable “0”

 

 

to normal

degree indication.

 

 

 

 

 

 

If the unit is not on generator, and the bypass

 

 

 

voltage otherwise appears normal, contact your

 

 

 

factory-authorized service provider.

 

 

The user adjustable maximum load alarm

 

 

 

threshold was exceeded. This is a “notification

Press “SILENCE” to silence the audible alarm.

 

 

only” type alarm, meaning the UPS takes no

 

 

Check the kW load % displayed for A phase.

 

 

action other than sounding an audible alarm

 

 

To check the setpoint for the alarm, press “Config,”

 

 

based on this setpoint. The setting allows the user

 

 

to monitor the load status of the UPS.

“User Settings,” “Adjustable Setpoints,” “Max Load

 

 

Alarm.”

Max Load Alarm

For example, if the current load on Phase A is

Compare the setpoint to the displayed load

Ph A

 

50%, the user can set this setpoint to 80% and an

 

 

alarm is received if the added load exceeds 80%.

percentage. If the load percentage displayed is

 

 

correct and the value exceeds the setpoint, raise

 

 

The alarm may also be configured with a delay, to

the setpoint to clear the alarm, or reduce the load

 

 

prevent nuisance alarms due to cycling loads.

below the setpoint.

 

 

The alarm is self-clearing. Once the load level

 

 

Contact your factory-authorized service provider.

 

 

decreases to less than 95% of the level setting,

 

 

 

 

 

the alarm clears.

 

 

 

 

 

 

 

The user adjustable maximum load alarm

 

 

 

threshold was exceeded. This is a “notification

Press “SILENCE” to silence the audible alarm.

 

 

only” type alarm, meaning the UPS takes no

 

 

Check the kW load % displayed for B phase.

 

 

action other than sounding an audible alarm

 

 

To check the setpoint for the alarm, press “Config,”

 

 

based on this setpoint. The setting allows the user

 

 

“User Settings,” “Adjustable Setpoints,” “Max Load

 

 

to monitor the load status of the UPS.

Alarm.”

Max Load

 

For example, if the current load on Phase B is

 

Compare the setpoint to the displayed load

Alarm Ph B

 

50%, the user can set this setpoint to 80% and an

 

percentage. If the load percentage displayed is

 

 

alarm is received if the added load exceeds 80%.

correct and the value exceeds the setpoint, raise

 

 

The alarm may also be configured with a delay, to

the setpoint to clear the alarm, or reduce the load

 

 

prevent nuisance alarms due to cycling loads.

 

 

below the setpoint.

 

 

The alarm is self-clearing. Once the load level

 

 

Contact your factory-authorized service provider.

 

 

decreases to less than 95% of the level setting,

 

 

 

 

 

the alarm clears.

 

 

 

 

 

 

 

The user adjustable maximum load alarm

 

 

 

threshold was exceeded. This is a “notification

Press “SILENCE” to silence the audible alarm.

 

 

only” type alarm, meaning the UPS takes no

 

 

Check the kW load % displayed for C phase.

 

 

action other than sounding an audible alarm

 

 

To check the setpoint for the alarm, press “Config,”

 

 

based on this setpoint. The setting allows the user

 

 

“User Settings,” “Adjustable Setpoints,” “Max Load

 

 

to monitor the load status of the UPS.

Alarm.”

Max Load

 

For example, if the current load on Phase C is

 

Compare the setpoint to the displayed load

Alarm Ph C

 

50%, the user can set this setpoint to 80% and an

 

percentage. If the load percentage displayed is

 

 

alarm is received if the added load exceeds 80%.

correct and the value exceeds the setpoint, raise

 

 

The alarm may also be configured with a delay, to

 

 

the setpoint to clear the alarm, or reduce the load

 

 

prevent nuisance alarms due to cycling loads.

below the setpoint.

 

 

The alarm is self-clearing. Once the load level

 

 

Contact your factory-authorized service provider.

 

 

decreases to less than 95% of the level setting,

 

 

 

 

 

the alarm clears.

 

 

 

 

 

 

 

The Module battery disconnect is open.

Press “SILENCE” to silence the audible alarm.

 

 

Check the status of Module Battery Disconnect

MBD Open

 

This alarm is self-clearing. When the condition is

 

(MBD). If it is open, the alarm is normal.

 

no longer present, the alarm and any control

 

 

If the Module Battery Disconnect is closed, contact

 

 

activity tied to the alarm reverts to normal.

 

 

your factory-authorized service provider.

 

 

 

 

 

 

 

58

Image 64
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions General Description Normal ModeModes of Operation Bypass Mode Battery ModeMaintenance Bypass OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Status Reports Menu Event ManagementStartup Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Reset MeteringHelp SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Load Transfer Procedures Transfer ProcedureRe-Transfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass Shutdown Procedures UPS Shutdown ProcedureSystem Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersBattery Maintenance UPS component service lifeLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery retorque values Torque specifications, unless otherwise labeled Detecting TroubleRack-Mounted Batteries Torque RequirementsUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Battery Operation Environmental specificationsParameter Specification Environmental ConditionsElectrical specifications Battery & DC ParametersLiebert NXL Model Size 250 Input ParametersSystem Parameter Liebert NXL Model SizePhysical Parameters & Standards, in mm Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ne t ItiTi n That