Emerson 250-400kVA manual Startup commands

Page 31

Operation

e.The “Close CB1” message will appear. Close CB1 (see Figure 2)

f.The “Press OK to Issue Rectifier On Command” message will appear. Press “OK” This will start the UPS’ rectifier. Load is still on internal bypass.

g.The “Press OK to Issue Inverter On Command” message appears. Press “OK”

The motorized Module Output Breaker (CB2) will close. The rectifier will be On and the Inverter will be on standby. Load is still on internal bypass.

h.The “Press OK to Issue Transfer Command” message appears. Press “OK” The load is now energized from the UPS Inverter.

NOTICE

Risk of equipment damage.If any abnormal situation occurs during this startup procedure, open the input circuit breaker and investigate the problem. Call Liebert Services if help is required.

4.When the Module DC Bus voltage is at 100%, you can manually close the module battery disconnect (MBD) circuit breaker (external to the UPS).

The Battery block in the Monitor/Mimic Display indicates the battery voltage and charge current.

NOTE

The battery charge current may increase quickly, but then should slowly decrease. If the system is recovering from a battery shutdown or an input power failure, the UPS rectifier will be recharging the battery. Recharge current can be more than 100 Amps. The maximum allowable recharge current for your unit will depend on the kVA rating and your factory-set battery recharge current limit.

! WARNING

Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment damage, personal injury and death.

Do not use equalize charging with valve-regulated, lead-acid batteries. Refer to the battery manufacturer’s manual, available on the manufacturer’s Web site, for specific information about equalize charging.

Figure 30 Startup commands

25

Image 31
Contents Liebert NXL Contacting Liebert for Support Battery Cabinet PrecautionsTable of Contents Specifications Figures Page Important Safety Instructions General Description Normal ModeModes of Operation Options Bypass ModeBattery Mode Maintenance BypassIntroduction Main component locations FeaturesMimic display Monitor/mimic display example Utility fail Monitor/mimic display example Normal power flowMonitor/mimic display example Load on bypass, UPS On Menu tree Touchscreen Navigation Main Display ScreenRating Parameters Configurations Menu RatingSystem Settings parameters User SettingsAdjustable setpoints parameters Adjustable SetpointsCell Count Adjustment Status Reports Menu Event ManagementStartup Menu Shutdown menu Shutdown MenuTransfer Menu Transfer/retransfer commandsTime remaining display Battery Management MenuDisplay summary see Figure Silence ResetMetering HelpLoad on bypass, UPS available OK to TransferInput power fail, load on battery Input Power Failure-Load on BatteryEmergency Module Off Off BatteryRemote Emergency Power Off Manual ProceduresStartup Procedure Startup commands Maintenance Bypass Load Transfers Load Transfer ProceduresTransfer Procedure Re-Transfer ProcedureMaintenance Bypass Load Transfers-If Load is on UPS Bypass Automatic Operations Shutdown ProceduresUPS Shutdown Procedure System Shutdown ProcedureCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Automatic Transfers to Bypass, UPS System FaultsSafety Precautions Routine Maintenance Liebert ServicesAir Filters Record LogComponent Expected Life Replace Battery MaintenanceUPS component service life Limited Life ComponentsBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery retorque values Torque Requirements Torque specifications, unless otherwise labeledDetecting Trouble Rack-Mounted BatteriesUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Environmental Conditions Battery OperationEnvironmental specifications Parameter SpecificationInput Parameters Electrical specificationsBattery & DC Parameters Liebert NXL Model Size 250System Parameter Liebert NXL Model SizePhysical Parameters & Standards, in mm Specifications Event Message Event Definition Recommended Action Liebert NXL alarm and status messagesObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page That Ne tIti Ti n