Emerson 250-400kVA manual Matching Battery Cabinets-Optional, Battery voltage, nominal and float

Page 42

Maintenance

Because individual battery characteristics are not identical and may change over time, the UPS mod- ule is equipped with circuitry to equalize battery cell voltages. This circuit increases charging voltage to maintain flooded type battery cells at full capacity.

! WARNING

Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment damage, personal injury and death.

Do not use equalize charging with valve-regulated, lead-acid batteries. Refer to the battery manufacturer’s manual, available on the manufacturer’s Web site, for specific information about equalize charging.

Matching Battery Cabinets—Optional

Although the individual battery cells are sealed (valve-regulated) and require only minimal mainte- nance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks should be performed at least annually to ensure years of trouble-free service.

Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS oper- ating, measure and record battery float voltage. With the DC circuit breaker open, measure and record the nominal (open circuit) voltage. Both these measurements should be made across the final positive and negative terminal lugs. Compare these values with those shown below. The recorded nominal voltage should be no less than the value shown; while the recorded float voltage should be within the range shown. If a discrepancy is found, contact Liebert Services.

Table 2 Battery voltage, nominal and float

 

Battery Voltage, VDC

Number of Cells

 

 

Nominal

Float

 

 

 

240

480

527 - 552

 

 

 

Power Connections: Check for corrosion and connection integrity. Visually inspect wiring for dis- colored or cracked insulation. Clean and/or retighten as required. Refer to torque specifications in Table 4.

Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and tighten if necessary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more than the retorque value. Table 8 shows battery retorque values.

Table 3

Battery retorque values

 

 

 

 

Battery

 

Battery Model

Retorque

Manufacturer

Number

Value

 

 

UPS12-300MR

110 in-lb

 

 

 

 

 

 

UPS12-350MR

110 in-lb

C&D batteries

 

 

UPS12-400MR

110 in-lb

 

 

 

 

 

 

UPS12-490MR

110 in-lb

 

 

 

 

 

 

UPS12-540MR

110 in-lb

 

 

 

 

 

 

HX205-FR

65 in-lb

 

 

 

 

 

 

HX300-FR

65 in-lb

Enersys

 

 

 

 

HX330-FR

65 in-lb

 

 

 

 

 

 

HX400-FR

65 in-lb

 

 

 

 

 

 

HX500-FR

65 in-lb

 

 

 

 

If you have a different model battery, contact Liebert Services for the required torque value.

To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts. The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.

When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and insulate the cables connected to the battery. Secure each battery shelf with retaining screws when maintenance is complete.

36

Image 42
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions Normal Mode General DescriptionModes of Operation Maintenance Bypass Bypass ModeBattery Mode OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Event Management Status Reports MenuStartup Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Help ResetMetering SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Re-Transfer Procedure Load Transfer ProceduresTransfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass System Shutdown Procedure Shutdown ProceduresUPS Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersLimited Life Components Battery MaintenanceUPS component service life Component Expected Life ReplaceBattery Safety Precautions Matching Battery Cabinets-Optional Battery voltage, nominal and floatBattery retorque values Rack-Mounted Batteries Torque specifications, unless otherwise labeledDetecting Trouble Torque RequirementsReporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Parameter Specification Battery OperationEnvironmental specifications Environmental ConditionsLiebert NXL Model Size 250 Electrical specificationsBattery & DC Parameters Input ParametersLiebert NXL Model Size System ParameterPhysical Parameters & Standards, in mm Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ti n Ne tIti That