Emerson 250-400kVA manual Displayed on the Module Output Meter. If

Page 54

 

 

 

UPS Alarm and Status Messages

Table 7

Liebert NXL alarm and status messages (continued)

 

 

 

Event Message

Event Definition

Recommended Action

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Observe the calculated load percentage on C phase

 

 

 

displayed on the Module Output Meter. If the

 

 

The critical load is greater than 110% while the

C phase steady state load percentage exceeds

 

 

110%, perform the following:

 

 

UPS is on bypass. The controls may shut the unit

 

 

If Maintenance Bypass is available, follow Standard

 

 

down if the overload condition does not clear

Operating Procedures to transfer the load to

 

 

within the allotted time. Allotted time is variable,

 

 

Maintenance Bypass.

 

 

and is inversely proportional to the amplitude of

Byp Overload

If Maintenance Bypass is not available but the

the overload, i.e., the greater the amplitude of the

Ph C

 

system has an Internal Bypass Breaker (CB3 on the

 

 

overload, the less time the unit continues to

One-Line Display), close CB3. Note that depending

 

 

support the load.

 

 

on the severity of the overload, the possibility exists

 

 

This alarm is self-clearing. When the condition is

 

 

that CB3 could trip if the overload exceeds the

 

 

no longer present, the alarm and any control

 

 

breaker rating.

 

 

activity tied to the alarm reverts to normal.

 

 

Investigate the overload condition.

 

 

 

 

 

 

If the Module Output Meter does not indicate an

 

 

 

overload condition, perform the previous steps and

 

 

 

contact your factory-authorized service provider.

Bypass Breaker

The bypass circuit breaker has failed to respond

 

(CB3) Close Fail

to a close signal.

 

Bypass Breaker

The bypass circuit breaker has failed to respond

 

(CB3) Open Fail

to an open signal.

 

Bypass Line Fail

The bypass source is not present.

 

 

 

 

 

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

 

Observe the One-Line Display. The bypass power

 

 

 

line feeding the static switch is green when bypass

 

 

 

power is within normal operating range. If the line

 

 

 

feeding the static switch is orange, gray, or black,

 

 

This summary event indicates a problem with the

bypass voltage is out of tolerance. Also check the

 

 

detected bypass voltage. If bypass is not

bypass voltage readings on the Bypass Meter.

Bypass Not Avail

available, transfers to bypass are disabled.

When the bypass returns to normal, this alarm

This alarm is self-clearing. When the condition is

clears automatically. If all indications checked

 

 

 

 

no longer present, the alarm and any control

above are normal and the alarm is still present,

 

 

activity tied to the alarm reverts to normal.

contact your factory-authorized service provider.

 

 

 

If there is a problem indicated with the bypass

 

 

 

voltage, investigate and resolve the issue.

 

 

 

Examples of conditions that could cause this alarm:

 

 

 

Unstable generator voltage; or, Bypass Feeder

 

 

 

Breaker tripped.

 

 

 

Press “SILENCE” to silence the audible alarm.

 

 

The bypass frequency has exceeded the bypass

Check the frequency on the Bypass Meter. If the

 

 

frequency is outside the synchronization range,

 

 

frequency limit of ± 5 Hz of nominal. If this alarm is

 

 

investigate and resolve the issue.

Bypass OF/UF

active, transfers to bypass are disabled.

This alarm is commonly the result of an uncalibrated

This alarm is self-clearing. When the condition is

 

 

generator, or power anomalies on the utility feed.

 

 

no longer present, the alarm and any control

 

 

Check bypass power for nominal limits.

 

 

activity tied to the alarm reverts to normal.

 

 

If bypass frequency appears normal, contact your

 

 

 

 

 

 

factory-authorized service provider.

 

 

 

 

 

 

This is a summary event that indicates a DSP

 

 

 

communication error.

Press “SILENCE” to silence the audible alarm.

Controller Error

The Controller Error event is a fault condition that

Press “RESET” to attempt to reset the fault.

 

 

indicates a loss of communications in the

Contact your factory-authorized service provider.

 

 

controls.

 

48

Image 54
Contents Liebert NXL Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Specifications Figures Page Important Safety Instructions Normal Mode General DescriptionModes of Operation Maintenance Bypass Bypass ModeBattery Mode OptionsIntroduction Features Main component locationsMimic display Monitor/mimic display example Normal power flow Monitor/mimic display example Utility failMonitor/mimic display example Load on bypass, UPS On Touchscreen Navigation Main Display Screen Menu treeConfigurations Menu Rating Rating ParametersUser Settings System Settings parametersAdjustable Setpoints Adjustable setpoints parametersCell Count Adjustment Event Management Status Reports MenuStartup Menu Shutdown Menu Shutdown menuTransfer/retransfer commands Transfer MenuBattery Management Menu Time remaining displayDisplay summary see Figure Help ResetMetering SilenceOK to Transfer Load on bypass, UPS availableInput Power Failure-Load on Battery Input power fail, load on batteryOff Battery Emergency Module OffManual Procedures Remote Emergency Power OffStartup Procedure Startup commands Re-Transfer Procedure Load Transfer ProceduresTransfer Procedure Maintenance Bypass Load TransfersMaintenance Bypass Load Transfers-If Load is on UPS Bypass System Shutdown Procedure Shutdown ProceduresUPS Shutdown Procedure Automatic OperationsAutomatic Transfers to Bypass Overload Condition Current-versus-time curves of overload capacityAutomatic Transfers to Bypass, UPS System Faults Automatic Retransfers to UPSSafety Precautions Liebert Services Routine MaintenanceRecord Log Air FiltersLimited Life Components Battery MaintenanceUPS component service life Component Expected Life ReplaceBattery Safety Precautions Matching Battery Cabinets-Optional Battery voltage, nominal and floatBattery retorque values Rack-Mounted Batteries Torque specifications, unless otherwise labeledDetecting Trouble Torque RequirementsReporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Parameter Specification Battery OperationEnvironmental specifications Environmental ConditionsLiebert NXL Model Size 250 Electrical specificationsBattery & DC Parameters Input ParametersLiebert NXL Model Size System ParameterPhysical Parameters & Standards, in mm Specifications Liebert NXL alarm and status messages Event Message Event Definition Recommended ActionObserve the One-Line Display. If the input line is Observe the One-Line Display. To identify which Do not Attempt to Close CB3 Until Reset Displayed on the Module Output Meter. If UPS controls monitor the DC Bus positive Resolve the issue that precipitated the EPO Check the One-Line Display for system status UPS, to transfer back to Inverter If this alarm occurs on an operational unit, it Attempt to manually close the disconnect by Module Output Meter. If the load is less than Output Power Factor. If the displayed power factor Until a service visit has been made and action taken When manual transfers are enabled Under normal conditions, no user action is required Observe the One-Line Display and the Active Event If the command to terminate Regeneration Mode If the alarm cannot be reset, or if the alarm condition UPS Alarm and Status Messages UPS Alarm and Status Messages Page Ti n Ne tIti That