Introduction
Environmental Specifications
The following environmental specifications are the same for both models of the PV100S 100 kW
Table 1-3 Environmental Specifications
Specification | Value |
|
|
Dimensions |
|
Inverter and DC Interface | 82 in H x 60 1/4 in W x 22 in D |
| (208 cm H x 153 cm W x 56 cm) |
Transformer and AC Interface | 44 in H x 50 in W x 34 in D |
| (112 cm H x 127 cm W x 86 cm D) |
Overall System Footprint: | 12 ft W x 6 ft L (approximate) |
Layout Option A | |
| (3.6 m x 1.8 m) |
Layout Option B | 9 ft W x 7 ft L (approximate) |
| (2.7 m W x 2.1 m L) |
|
|
Weight |
|
Inverter and DC Interface | 1000 lbs (approximate) |
Transformer and AC Interface | 1400 lbs (approximate) |
Overall Weight | 2400 lbs (approximate) |
|
|
Allowable Ambient Temperature |
|
Operating | |
Storage | |
|
|
Relative Humidity | To 95%, |
Elevation | Power Derated above 6600 ft |
|
|
Clearance (ventilation and | In front of access doors: 36 in (91 cm) |
serviceability) | In front of access panels: 36 in (91 cm) |
| |
| Sides: 12 in (30 cm) |
| Back: 6 in (15 cm) |
|
|
Maximum Distance between Main | 15 ft (4.5 m) |
Inverter Enclosure and AC |
|
Interface/Transformer Enclosure |
|
|
|
152315 Rev C |