Planning
Ground Requirements
This product is intended to be installed as part of a permanently grounded electrical system per National Electric Code ANSI/NFPA 70. A copper ground rod must be installed within three feet of the PV100S enclosure. This is the single point earth ground for the inverter system. The single point ground for the system is to be made at the AC ground bus bar (TB2) in the AC Interface Enclosure.
System Neutral Requirements
The PV100S is designed to be installed as a
Communication Requirements
The PV100S can accommodate any one of the following options for PC
Communication:
•POTS Connect Kit - uses a MultiTech® 56K Modem, RS232/Fiber Optic Converter (configured for ethernet) and SA2 Surge Arrestor. A direct analog phone line to the local phone service is required to use this feature. The phone line used for PV100S communication cannot be routed through a Private Branch Exchange (PBX) unless an analog PBX card is used.
•Wireless Connect - uses a GSM Wireless Modem.
•Ethernet LAN Connect - uses a data communication device to enable the unit to connect to a local area network.
•Direct Connect Kit - uses a RS232/Fiber Optic Converter (configured for a PC), a
Determine which communications options are required for the installation and procure the appropriate service or phone access. The personal computer to be used with this unit must have the appropriate hardware as well, such as a 56K modem for dial up connection or a Network Interface Card (NIC) for a LAN connection.
Utility Side Isolation Transformer Requirements
The PV100S is supplied with a custom,
152315 Rev C |