Wiring - General
Overcurrent Protection
AC overcurrent protection for the Utility Interconnect
CAUTION: Equipment Damage
In accordance with the NEC, ANSI/NFPA 70 (Ninth Edition) the following
•400A maximum for
•200A maximum for
Conductor Termination
| The PV100S has terminals and bus bars for making all wiring connections |
| required for the installation. All terminals used for making AC and DC |
| connections require the use of copper conductors with an insulation rating of |
| 90 °C (or higher). For wire gauge, bolt size, and torque values for the AC |
| terminals, see Table |
| terminals, see Table |
Transformer | The AC terminals in the Transformer Enclosure |
Enclosure | require the use of |
| are one bolt per pole. |
| See Figure |
Main Inverter | The AC terminals in the Main Inverter Enclosure |
Enclosure | have two openings per pole. These terminals do not require the use of |
| type ring terminals or compression lugs. |
| See Figure |
AC Interface | The AC line terminals in the AC Interface Enclosure |
Enclosure | |
| ring terminals or compression lugs. |
| See Figure |
| The AC neutral terminal in the AC Interface Enclosure (TB6) has one bolt per |
| pole and requires the use of |
| See Figure |
DC Interface | The DC terminals in the DC Interface Enclosure |
Enclosure | have two openings per pole. These terminals do not require the use of |
| type ring terminals or compression lugs. |
| See Figure |
|
|
| Important: Keep these cables together as much as possible, and ensure that all cables |
| pass through the same knockout and conduit fittings, thus allowing any inductive currents |
| to cancel. |
152315 Rev C |