Anchoring the PV100S
Anchoring the PV100S
The PV100S is designed to be installed in either an indoor or outdoor location. It must be placed on and anchored to a level concrete floor or pad. The concrete floor or pad, upon which the PV100S is anchored, must be structurally designed to meet any local, state, or national requirements for weight, seismic, and wind sheer if applicable.
Four 5/8" holes are provided in the feet of the main inverter, and six 5/8" holes are provided in the feet of the AC interface/transformer assembly for anchoring to the floor or pad.
Figure 2-9 and Figure 2-10 depict the layout patterns of the anchoring holes for both the PV100S main inverter and the AC interface/transformer assembly.
29" (73.7 cm)
5/8"
(1.5 cm)
(x4)
16¼"
(40.6 cm)
Figure 2-9 Main Inverter Anchor Bolt Pattern (Not to scale)
152315 Rev C |