Chg Bad AC Qlty

Troubleshooting

Table 6-3Error Messages

Error Message

Details

Action

 

 

 

Chg Bad AC Qlty

In Charger or Bypass mode the

Test the PROsine with a good quality generator

 

PROsine is being powered from an

or the AC utility to verify whether the normal

Byp Bad AC Qlty

incompatible AC source, probably a

generator is the problem. If so, enabling charge

 

 

very low quality generator. The

mode and turning on a DC load (e.g. a light)

 

PROsine is compatible with virtually all

should allow the PROsine to operate correctly

 

nominal 120V 60Hz AC sources

from any generator which is not defective. If it is

 

(including Modified Sine Wave) but it

a small generator and is unable to supply all the

 

is possible that a very low quality

current the PROsine might demand, the AC

 

source may cause a problem in some

Breaker Size rating in the Configure PROsine

 

operating conditions. If these errors

— Basic Menu can be lowered so as not to

 

occur the PROsine will disconnect from

overload the generator.

 

the AC source because it is unsafe to

 

 

continue to operate the PROsine from

 

 

that source - and it may cause problems

 

 

for some AC loads as well.

 

 

 

 