Part 3: Configuration Options

Configure PROsine—Basic Menu

Menu Items

Access

 

 

AC Breaker Size

User

 

 

Load Sensing

User

 

 

Equalize

User

 

 

Menu Choices or Information Displayed

AC Breaker Size

Set the AC breaker size to match the shorepower circuit breaker size to reduce

 

circuit breaker “nuisance” tripping. Values range from 0–30 amps.

Load Sensing

Select Enabled if you want the unit to only turn on when a load is present. In

 

Load Sense mode, the unit will periodically search for the presence of an AC load

 

while it is inverting. The unit will “sleep” if the load it detects is less than the

 

Load Sensing setting or if there is no load.

 

Select Disabled if you want the inverter on full-time rather than only when a load

 

is present.

 

For further information about load sensing, see “Load Sensing Mode” on page 5–

 

5.

Equalize

Select Enabled or Disabled. You can only select Enabled when the unit is

 

charging and battery type is set to Flooded.

 

An equalization charge must only be performed on flooded (non-sealed or “wet”)

 

batteries and only as often as recommended by the battery manufacturer.

WARNING: Fire hazard

If you select Enabled, you must monitor the electrolyte specific gravity and level during the equalization phase to prevent over-heating and battery damage.

CAUTION

During the equalization phase, the DC system voltage may exceed 17VDC, and therefore you should disconnect any sensitive DC loads.

445-0089-01-01