Part 3: Configuration Options
Configure PROsine—Basic Menu
Menu Items | Access |
|
|
AC Breaker Size | User |
|
|
Load Sensing | User |
|
|
Equalize | User |
|
|
Menu Choices or Information Displayed
AC Breaker Size | Set the AC breaker size to match the shorepower circuit breaker size to reduce |
| circuit breaker “nuisance” tripping. Values range from |
Load Sensing | Select Enabled if you want the unit to only turn on when a load is present. In |
| Load Sense mode, the unit will periodically search for the presence of an AC load |
| while it is inverting. The unit will “sleep” if the load it detects is less than the |
| Load Sensing setting or if there is no load. |
| Select Disabled if you want the inverter on |
| is present. |
| For further information about load sensing, see “Load Sensing Mode” on page 5– |
| 5. |
Equalize | Select Enabled or Disabled. You can only select Enabled when the unit is |
| charging and battery type is set to Flooded. |
| An equalization charge must only be performed on flooded |
| batteries and only as often as recommended by the battery manufacturer. |
WARNING: Fire hazard
If you select Enabled, you must monitor the electrolyte specific gravity and level during the equalization phase to prevent
CAUTION
During the equalization phase, the DC system voltage may exceed 17VDC, and therefore you should disconnect any sensitive DC loads.