Part 1: System Startup Check

Operation

Part 1: System Startup Check

WARNING

Review the “Important Safety Instructions” on page vii before operating the PROsine.

To test the charging and inverting functions:

1.Close the battery disconnect and turn on the PROsine’s ON/OFF/REM switch.

2.To test the inverter, set the INVERTER switch to ENABLE and disconnect the AC input source breaker.

3.Place a load on the inverter (e.g. plug a light into an outlet that the inverter is powering) and make sure it works. The INVERTING LED should come on and the inverter should run the load using battery power.

4.To test the charger, connect the AC input source breaker. Set the display’s CHARGER switch to ENABLE. After a short delay, the CHARGING LED should come on. Any AC loads powered by the inverter will also work at this time.

5.Remove the AC shorepower. The PROsine should transfer to Inverter mode immediately. (The transfer relay will make a clicking sound and the INVERTING LED will come on.) Loads should continue to operate uninterrupted.

If any part of this procedure fails, determine the cause before using the PROsine. Consult the Chapter 6, “Troubleshooting”.