Configuration
Configure PROsine—Advanced Menu
Menu Display | Menu Items | Access |
(if different from Menu Item) | ||
|
|
|
| Load Sensing | User |
|
|
|
| Load Sense Power | User |
|
|
|
| Load Sense Interval | User |
|
|
|
| Low AC Transfer (V) | User |
|
|
|
| Low AC Transfer (Hz) | User |
|
|
|
High AC Transfr (V) | High AC Transfer (V) | User |
|
|
|
High AC Transfr (Hz) | High AC Transfer (Hz) | User |
|
|
|
| AC Series Mode | Installer |
|
|
|
| Inverter Low V Shutdown | User |
|
|
|
| Inverter Low V Warning | User |
|
|
|
INV Low V Restrt Hyst | Inverter Low V Restart Hysteresis | User |
|
|
|
| Run Without Panel | User |
|
|
|
| Inverter After Reset (Without Panel) | User |
|
|
|
| Charger After Reset (Without Panel) | User |
|
|
|
| Auto Restart After Error | User |
|
|
|
Reset to Dflts | Reset to Defaults | Installer |
|
|
|
Menu Choices or Information Displayed
Load Sensing | Select Enabled if you want the unit to periodically search for the presence of an |
| AC load while it is inverting. The unit will “sleep” if the load it detects is less than |
| the Load Sensing setting. |
| Select Disabled if you do not want the unit to search for an AC load. |
| For further information about load sensing, see “Load Sensing Mode” on page 5– |
| 5. |
Load Sense Power | This setting determines what power the inverter needs to detect before it will start |
| automatically (if Load Sensing is Enabled). Settings range between 10 and |
| 255W. |
Load Sense Interval | This is the amount of time between checks for the presence of an AC power load. |
| To save power while the unit is load sensing, increase the interval. The range is |
| 0.5 to 25 seconds. |