Part 3: Configuration Options

 

Part 3: Configuration Options

 

 

Low AC Transfer

This is the voltage below which the unit will no longer recognize AC as “good”,

(V)

will open the relay, and will attempt to transfer to Invert mode if Invert is

 

Enabled. The range of values is 85–110Vac.

Low AC Transfer

This the frequency at which the unit will no longer recognize AC as “good” and

(Hz)

will attempt to transfer to Invert mode. The range is 40–59Hz.

High AC Transfer

This is the voltage above which the unit will no longer recognize AC as “good”

(V)

and will attempt to transfer to Invert. The range is 120–135Vac.

High AC Transfer

This the frequency at which the unit will no longer recognize AC as “good” and

(Hz)

will attempt to transfer to Invert. The range is 61–70Hz.

AC Series Mode

Select Standalone if you are operating a single PROsine to produce 120V single

 

phase.

 

If you are installing two PROsines as a 240 split-phase system, set one PROsine

 

as Master and the other as Slave.

Inverter Low V

At or below this battery voltage, the inverter will shut down. The values range

Shutdown

from 10–16Vdc.

Inverter Low V

This is an offset voltage ranging from 0 to 3.0V. When the battery voltage drops

Warning

below the sum of Low V Shutdown and Low V Warning, the PROsine will

 

sound a warning.

Inverter Low V

This is an offset voltage ranging from 0.5 to 2.5V. When the unit has shut down

Restart Hysteresis

due to low battery voltage it will not automatically restart until the battery voltage

 

recovers to the sum of Inverter Low V Shutdown and Inverter Low V Restart

 

Hysteresis. When the PROsine shuts down the battery voltage will rise and may

 

cause the PROsine to restart, which drops the voltage again so the PROsine shuts

 

down, etc. This hysteresis setting reduces this problem. The default value is 2.5V

 

and should not be changed unless there is a special reason for doing so or this

 

problem will return.

Run Without Panel

Select Yes if you want the PROsine to continue running if the display panel is

 

disconnected or the communication cable is damaged.

Inverter Enabled on

Select Yes if you want the inverter to be enabled on startup if no panel is detected

Reset Without Panel

after 10 seconds.

Charger Enabled on

Select Yes if you want the charger to be enabled on startup if no panel is detected

Reset Without Panel

after 10 seconds.