| Part 3: Configuration Options |
|
|
Low AC Transfer | This is the voltage below which the unit will no longer recognize AC as “good”, |
(V) | will open the relay, and will attempt to transfer to Invert mode if Invert is |
| Enabled. The range of values is |
Low AC Transfer | This the frequency at which the unit will no longer recognize AC as “good” and |
(Hz) | will attempt to transfer to Invert mode. The range is |
High AC Transfer | This is the voltage above which the unit will no longer recognize AC as “good” |
(V) | and will attempt to transfer to Invert. The range is |
High AC Transfer | This the frequency at which the unit will no longer recognize AC as “good” and |
(Hz) | will attempt to transfer to Invert. The range is |
AC Series Mode | Select Standalone if you are operating a single PROsine to produce 120V single |
| phase. |
| If you are installing two PROsines as a 240 |
| as Master and the other as Slave. |
Inverter Low V | At or below this battery voltage, the inverter will shut down. The values range |
Shutdown | from |
Inverter Low V | This is an offset voltage ranging from 0 to 3.0V. When the battery voltage drops |
Warning | below the sum of Low V Shutdown and Low V Warning, the PROsine will |
| sound a warning. |
Inverter Low V | This is an offset voltage ranging from 0.5 to 2.5V. When the unit has shut down |
Restart Hysteresis | due to low battery voltage it will not automatically restart until the battery voltage |
| recovers to the sum of Inverter Low V Shutdown and Inverter Low V Restart |
| Hysteresis. When the PROsine shuts down the battery voltage will rise and may |
| cause the PROsine to restart, which drops the voltage again so the PROsine shuts |
| down, etc. This hysteresis setting reduces this problem. The default value is 2.5V |
| and should not be changed unless there is a special reason for doing so or this |
| problem will return. |
Run Without Panel | Select Yes if you want the PROsine to continue running if the display panel is |
| disconnected or the communication cable is damaged. |
Inverter Enabled on | Select Yes if you want the inverter to be enabled on startup if no panel is detected |
Reset Without Panel | after 10 seconds. |
Charger Enabled on | Select Yes if you want the charger to be enabled on startup if no panel is detected |
Reset Without Panel | after 10 seconds. |