Configuring a Series System
Configuring a Series System
Configure each PROsine through its display panel. Refer to “Part 2: Configuration Menus and Screens” on page
To configure the series system
1.Set up the usual parameters (battery size and type, AC transfer conditions, etc.) and make sure both PROsines are configured the same.
2.Select one unit to be the “master” and the other to be the “slave”. Configure AC Series Mode (on the PROsine Advanced menu) as master SP and slave SP respectively. (SP refers to “Split Phase.”)
Any 120Vac loads that require the fastest possible transfer should be powered by the “master” unit.
3.If the two PROsines are connected to the same battery bank, configure Charger Mode (on the Battery menu) to be Primary for the master and Secondary for the slave. If the two PROsines are connected to separate battery banks, set Charger Mode to Standalone for both PROsines.
Your system is now ready for operation.