Xantrex Technology PROsine 2.0 user manual Connections for Single Hardwire Output With GFCI, Gfci

Models: PROsine 2.0

1 148
Download 148 pages 27.01 Kb
Page 58
Image 58
Connections for Single Hardwire Output With GFCI

Installation

Connections for Single Hardwire Output With GFCI

Figure 3-6 is a cutaway top view of the PROsine wiring compartment showing one set of outgoing AC wires with the GFCI option.

To make the AC output wiring connections

1.Run 10AWG 2-conductor-plus-ground through one of the cable clamps on the AC end.

2.Strip about two inches of the jacket from the AC cable and separate the wires. Strip insulation from each of the wires according to the guidelines given by the connector manufacturer.

3.Connect the outgoing black and white (line and neutral) AC wires to the PROsine black and white AC output wires.

4.Connect the outgoing ground wire to the chassis using one of the screws marked GFCI.

5.Tuck the wires into the left-hand side of the wiring compartment so they don’t interfere with the GFCI assembly.

WARNING: Shock hazard

If you are not using the hardwire output circuit, you must cap off its line and neutral wires. Use twist-on wire nuts where allowed; use crimp-on wire caps in other applications.

grounding screw

Cutaway view of

 

PROsine 2.0 wiring

compartment as

seen from the top.

outgoing

 

AC cable

wire nuts or crimp-on

 

 

wire caps (depending

 

on type of installation)

Figure 3-6Single Hardwire Output With GFCIDo not disturb factory wiring.

Manual backgroundManual backgroundGFCI

Figure 3-6Single Hardwire Output With GFCI