Installation

Connections for Single Hardwire Output With GFCI

Figure 3-6 is a cutaway top view of the PROsine wiring compartment showing one set of outgoing AC wires with the GFCI option.

To make the AC output wiring connections

1.Run 10AWG 2-conductor-plus-ground through one of the cable clamps on the AC end.

2.Strip about two inches of the jacket from the AC cable and separate the wires. Strip insulation from each of the wires according to the guidelines given by the connector manufacturer.

3.Connect the outgoing black and white (line and neutral) AC wires to the PROsine black and white AC output wires.

4.Connect the outgoing ground wire to the chassis using one of the screws marked .

5.Tuck the wires into the left-hand side of the wiring compartment so they don’t interfere with the GFCI assembly.

WARNING: Shock hazard

If you are not using the hardwire output circuit, you must cap off its line and neutral wires. Use twist-on wire nuts where allowed; use crimp-on wire caps in other applications.

grounding screw

Cutaway view of

 

PROsine 2.0 wiring

compartment as

seen from the top.

outgoing

 

AC cable

wire nuts or crimp-on

 

 

wire caps (depending

 

on type of installation)

Do not disturb factory wiring.

GFCI

Figure 3-6Single Hardwire Output With GFCI

3–16

445-0089-01-01

Page 58
Image 58