Troubleshooting
Error Messages
Error messages indicate that there has been a change in system operation due to a detected condition.
•You can retrieve the previous twenty Error messages by placing the unit in Configure mode and then selecting View Last 20 PROsine Faults from the Diagnostics menu.
•To clear an Error message, press the ESCAPE key.
•If the audible alarm is enabled, press ESCAPE twice. The first key press deactivates the alarm and the second removes the message from the screen. (The error is not cleared from the system, however.)
Some Error messages appear as
Internal nnnn
where nnnn is the number of the error.
If one of these errors causes the PROsine to shut down, attempt to restart the unit. If the error occurs again, call Xantrex.
Other errors are listed in <Xref>Table
Table 6-3 Error Messages
Error Message | Details | Action | |
|
|
| |
Low Bus Voltage |
| Clear the error in the Configure menu and then | |
|
| recharge the batteries. | |
Invert Lo Bus V |
| ||
Low bus voltage detected | If the batteries are fully charged then verify that | ||
| |||
Bypass Lo Bus V |
| the DC cables are the correct size and that all | |
|
| connections are tight. | |
|
|
| |
Battery Too Hot | PROsine battery temperature too high. | Check the tightness of all connections. | |
|
| Check electrolyte level. | |
|
| Check charger and battery settings. | |
|
|
| |
Battery TooCold | PROsine battery temperature too low. | Extreme cold may require a battery heater. If the | |
|
| battery is frozen, thaw it gradually to avoid | |
|
| damage. | |
|
|
| |
Temp1 Too Hot | PROsine internal temperature 1 too | Reduce the loads on the system. | |
| high. | Ensure that the PROsine is being adequately | |
|
| ventilated. | |
Temp2 Too Hot | PROsine internal temperature 2 too | ||
| |||
| high. |
| |
|
|
| |
Temp1 Too Cold | PROsine internal temperature 1 too low. | Raise the ambient temperature. | |
|
| ||
Temp2 Too Cold | PROsine internal temperature 2 too low. | ||
| |||
|
|
| |
Invert Lo Bat V | Inverter battery voltage low (below | Check battery state of charge and | |
| configured shutdown level or below 8V | necessary. | |
Inv Low Bat V FS | |||
for Fault Shutdown). | Check for proper DC cable size. | ||
| |||
|
| Check all connections for tightness. | |
|
|
|