| Part 3: Configuration Options |
|
|
|
Equalize Mode | • | Max Voltage |
Settings |
| This is the maximum available charging voltage for the Equalize charging |
|
| stage. |
| • | Max Current (%C) |
|
| This is the maximum available charging current (in A) as % of battery |
|
| capacity in (Ah) for the Equalize charging stage. |
| • | Max Timeout |
|
| This is the maximum amount of time that the unit will stay in Equalize stage. |
| • | Threshold Change and Timeout |
|
| When the battery voltage changes by less than the change value over the |
|
| Threshold Timeout specified, the unit goes to Float charging. |
Constant Mode |
| Voltage and current setpoints will be set, but the unit will likely be able to |
Settings |
| satisfy only one of these setpoints at any given time. |
|
| Example: For setpoints of 13.5V and 50A, the unit will supply 13.5V up to |
|
| 50A and at higher loads, the current is held at 50A and the voltage will drop. |
| • | Voltage Setpoint |
|
| The PROsine will attempt to charge the battery at this target voltage. The |
|
| default value is 13.5V. |
| • | Current Setpoint |
|
| The PROsine will attempt to charge the battery at this target current. The |
|
| default value is 100A. |
| • | Exit Criteria |
|
| None. Unless a fault occurs, the unit will run continuously. Care must be |
|
| taken to ensure that the voltage and current setpoints are correct for your |
|
| battery type and loads to avoid damage. |
Charger Mode | Select Standalone when a single PROsine is being used to charge a battery. | |
| When multiple PROsines are charging a single battery bank, the secondary | |
| chargers only operate during the Bulk charge phase, and the primary charger | |
| finishes charging the battery. | |
| In this situation, select one charger as primary and all others as secondary. | |
| p | Standalone |
| p | Primary |
| p | Secondary |