Warning Messages
Table 6-2 Warning Messages
Warning Message | Details | Action | |
|
|
| |
Inv Hi Bat V | High battery voltage, invert mode. | Check for external charging sources and disable | |
|
| ||
Chg Hi Bat V | Battery voltage exceeds 15.5V in | ||
if necessary. | |||
| charge mode. |
| |
|
|
| |
AC In Rev Pol | Input AC line and neutral wiring | The unit will continue to operate. For safest | |
| polarity is reserved. Check to see that | operation, however, you should correct the AC | |
| the Line side of the AC source | input wiring | |
| (shorepower) has a voltage to ground |
| |
| and the neutral side does not. May also |
| |
| occur if the shorepower neutral is |
| |
| floating (not connected to earth) |
| |
|
|
| |
AC Out Ovrload | AC output overload. | Reduce the AC load so that even for short times, | |
|
| AC output current does not exceed 26A. | |
|
|
| |
Low AC In V | AC input voltage too low. | Check for bad cabling. | |
|
| There may be too many loads on the AC supply | |
|
| line. | |
|
| Reduce the AC dropout level. | |
|
|
| |
High AC In V | AC input voltage too high. | Check the AC input (shorepower) source voltage | |
|
| and correct if necessary or raise the AC input | |
|
| high voltage limit. | |
|
|
| |
Bat Temp Short | Battery temperature sensor short | Install a new sensor. | |
| detected. |
| |
|
|
| |
Memory Warning | EEPROM memory CRC is incorrect | Call Xantrex. | |
|
|
| |
Equalizing! | The unit is equalizing. | Refer to page | |
|
| loads and monitor battery electrolyte level and | |
|
| S.G. throughout. | |
|
|
| |
Unit attempting to | Auto Restart After Error has been | The unit will | |
restart. | enabled, the error has cleared, and the | output without warning. | |
| unit is restarting. | Disconnect any AC loads that could be | |
|
| hazardous if they were to become | |
|
| without warning. | |
|
|
|