Part 3: Configuration Options

Menu Choices or Information Displayed

 

 

WARNING: Risk of Fire or Explosion

 

 

Incorrect settings can damage or destroy your batteries. When making any battery

 

 

configuration settings, ensure that the values are correct according to the battery

 

 

manufacturer’s specifications. Settings should be changed by qualified personnel only.

 

 

 

 

 

The Configure Battery menu lets you read (as a user) and change (installer-only)

 

 

settings associated with the battery system. The parameters that can be set include

 

 

battery size, temperature, and type.

Battery Size

This is the capacity of the battery or battery bank in ampere-hours. The PROsine

 

 

will alter the charging rate based on battery bank size. Charging at a rate that is too

 

 

high for your batteries can damage or destroy them.

 

 

Select the appropriate value between 50 and 2000 Ah.

Default Batt Temp

Select a battery temperature that is closest to the average ambient temperature in

 

 

the location where the battery is installed. The choices are:

 

 

p

Cold: 5°C (41°F)

 

 

p

Warm: 20°C (68°F)

 

 

p

Hot: 35°C (95°F)

 

 

When the battery temperature sensor is installed, this setting is ignored and the

 

 

actual battery temperature is used.

Battery Type

From the list of options available, select the type of battery(s) that you have

 

 

installed. See Application Note: Battery Banks for Inverter Systems (976-0114-

 

 

01-01).

 

 

When you select a charging algorithm, the battery details listed below (see “View

 

 

/ Change Battery Details” on page 4–13) are automatically given default settings.

 

 

These default values are the most appropriate for the selected battery type.

 

 

 

If you have a battery type that isn’t on the list, you can modify the charging

 

 

 

algorithm settings according to the manufacturer’s guidelines. (This requires

 

 

 

you to be in Installer mode.)

View / Change

The screens associated with these menu items display information about the way

Battery Details

the PROsine will charge the battery.

Battery Temp

This is the relationship between temperature and voltage levels on the battery. The

Coefficient

correct value depends on battery type. For the correct value, consult the battery

 

 

manufacturer.

445-0089-01-01

4–13

Page 81
Image 81