Rear Panels (continued)
10.“Battery Start” Switch: This momentary rocker switch allows you to
11.AC Input Breaker: Controls input power to the UPS during normal operation.
12.Bypass AC Input Breaker: Controls input power to the UPS during “BYPASS” operation.
13.Remote “Emergency Power OFF” (EPO) Connector: This modular jack allows remote emergency shutdown. See “Communications” for details.
14.Inverter Operation DIP Switches: Behind this removable panel are four DIP Switches that should be set to match your input voltage and input frequency. Your input voltage and frequency DIP switch settings MUST match your input. Your UPS WILL NOT CONVERT the voltage or frequency.
15.Grounding Terminal: This terminal connects to a grounding electrode conductor. IT IS NOT SAFE TO OPERATE YOUR UPS WITHOUT CONNECTING IT. The recommended conductor size is 6 AWG based on the UL 1778 standard. Follow all applicable local electrical wiring regulations.
16.Stabilizers: These supports extend to keep your UPS from rolling or tipping.
17.Battery Module Input Connector: Use this connector to
18.Battery Module Output Cable: Use this cable to connect the battery module to the power module (or to another battery module when using more than one). The power module will not start without a connection to a charged battery module. Refer to the battery module owner's manual for connection instructions and safety warnings.
19.Tower Mounting: For additional stability during tower mounting of BP240V10RT3U External Battery Module, you can order Tripp Lite base stands (model #:
Installation
INVERTER OPERATION DIP SWITCH SETTINGS
Using a small tool, set the four Inverter Operation DIP Switches (located on the rear panel of your UPS) to match your input voltage, input frequency and desired operational mode.
Input Voltage Selection
(DIP Switches #1 & #2)
These DIP switches must be set to match your input voltage. Your UPS WILL NOT CONVERT the voltage.
Input Voltage | DIP Switch Position |
|
|
220V | #1 UP & #2 DOWN |
|
|
230V | #1 DOWN & #2 UP |
|
|
240V | #1 DOWN & #2 DOWN |
|
|
Input Frequency Selection
(DIP Switch #3)
Your Input Frequency setting MUST match your input frequency. Your UPS WILL NOT CONVERT the frequency.
Input Frequency | DIP Switch Position |
|
|
50 Hz | #3 UP |
|
|
60 Hz | #3 DOWN |
|
|
1 2 3 4
220V
1 2 3 4
230V
1 2 3 4
240V
1 2 3 4
50 Hz
1 2 3 4
60 Hz
REFER TO USER'S MANUAL FOR TORQUING
SPECIFICATIONS, USE COPPER CONDUCTORS ONLY. UTILISER SEULEMENT LES CONDUCTEURS DE CUIVRE.
5