Overview
Mounting the Mount the remote output module horizontally (so the F2DO logo on the front panel
Remote Output is facing the user) to allow sufficient ventilation. We advise not to mount the remote
Moduleoutput module in a vertical position, because in this case additional measures are required to ensure the device does not move.
The minimum distance to any neighboring device from another manufacturer is as follows:
vertical space of at least 100 mm (3.93 in.),
horizontal space of at least 20 mm (0.78 in.).
Minimum clearances for the XPSMF2DO801 safety remote output module (Compact Devices):
mm
inch
HIMatrix by HIMA
F3
HIMA |
HIMatrix by HIMA
F31
HIMA |
100 | 3.94 |
| 20 |
|
|
| |
|
|
| 0.79 |
| HIMatrix | by HIMA | by HIMA |
| F30 | HIMatrix F3 | |
HIMA |
|
| HIMA |
Note: The installation must be performed so that
the device is not subject to heat emission from neighboring devices and
devices with high EMC interference do not affect the XPSMF2DO801.
Heat emission and electromagnetic compatibility (EMC) must be checked for devices from other manufacturers to ensure that operation of the remote output device is not affected by any external device.
The overall installation space for all cables must also be taken into account to ensure sufficient ventilation. Additional measures, such as installing heat extraction fans, can be taken if the product’s housing becomes warm.
14 | 33003405 07/2007 |