Equipment Description
Operating Conditions
Overview | The XPSMF2DO801 safety remote output module has been developed in | |
| compliance with the requirements of the following standards for EMC, climate and | |
| environment: |
|
|
|
|
| IEC | Programmable Controllers, Part 2, Equipment Requirements and |
|
| Tests |
|
|
|
| IEC | EMC Generic Standards, Part |
|
|
|
| IEC | EMC General Emission Standard, Industrial Environment |
|
|
|
To use the XPSMF2DO801 safety remote output module, the following conditions must be fulfilled:
| Protection Class | Protection class II according to IEC/EN |
|
|
|
| Pollution | Pollution degree II |
|
|
|
| Altitude | < 2000 m / 6561.7 ft |
|
|
|
| Enclosure | Standard: IP 20 If requested by the relevant application standards |
|
| (e.g., EN 60204, EN |
|
| enclosure (e.g., IP 54). |
|
|
|
|
|
|
|
|
|
|
|
|
Climatic | The most important tests and limit values for climatic conditions are listed in the | |
Conditions | following table: |
|
|
|
|
| EN | Climatic Tests |
|
|
|
|
| Operating temperature: 0°C to 60°C / 32°F to 140°F |
|
| (Test limits |
|
|
|
|
| Storage temperature: |
|
| only |
|
|
|
| 6.3.4.2 | Dry heat and cold withstand test: 70°C / |
|
| EUT power supply disconnected |
|
|
|
| 6.3.4.3 | Change of temperature, withstand and immunity test: |
|
| |
|
| disconnected |
|
|
|
| 6.3.4.4 | Cyclic damp heat withstand test: 25°C / 55°C (77°F / 131°F), 95% |
|
| relative humidity, EUT power supply disconnected |
|
|
|
|
|
|
|
|
|
|
|
|
56 | 33003405 07/2007 |