Schneider Electric XPSMF2DO801 manual Index

Page 81

A

additional items, 62 air circulation, 15 application, 25

B

block diagram, 26

C

cable disconnection, 29 climatic conditions, 56 communication, 40 configuration

Ethernet interfaces, 73 connections for SafeEthernet, 53

D

description of error codes, 68 diagnostics, 31 dimensions, 11

E

EMC conditions, 57 equipment description, 35 error codes, 68 Ethernet

configuration, 73

Ethernet communication used network ports, 53

F

first power-up, 24 front view, 10, 36 function, 26

H

heat, 18

housing elements, 36

I

initial operation, 24 installation, 13 interface elements, 47 internal convection, 20 introduction, 10

IP addressing and system ID, 49

L

large system reconfiguration, 30 LED description, 45

LEDs, 44

list of additional items, 62

33003405 07/2007

81

Image 81
Contents 07/2007 XPSMF2DO801 Remote Output Module Hardware ManualPage Table of Contents At a Glance AppendicesSafety Information ProcedureImportant Information Safety Information At a Glance About the Book33003405 07/2007 Overview XPSMF2DO801 Overview Whats in this Chapter?Topic Representation IntroductionFront View ModuleDimensions Remote output module DimensionsSide View Procedure InstallationIntroduction Step ActionHIMatrix 100 Compact device Cable duct Spacer Length of the required spacer is calculated as follows Installation with spacers= H 40 mm / 1.57 = length of the spacer = height of the cable ductHIMatrix F31 Heat Case installation Calculation of a m2 1m2=10.76ft2 Internal HousingConvection Variable DescriptionTemperature range Temperature state Temperature State/OperatingOverview Application and Function Initial Operation XPSMF2DO801 safety remote output moduleOverview StageApplication Function Terminal No Designation Function relay output Application and Function Disconnection CableFollowing will occur SystemLarge System Reconfiguration Power Supply InterruptionVoltage level Reaction of the controller StepSHORT-CIRCUIT Condition Short-Circuit Characteristics Output ChannelsModules Offline Proof Test Offline Proof-Test Periodic Proof TestingExecution Offline ProofOutput module Equipment DescriptionWhats in this Chapter?Housing Elements XPSMF2DO801 safety remote output moduleElements of the front panel Top View Following image shows the elements of the top panel Back Panel Following image shows elements of the back panel Using Reset Reset ButtonHousing, about 40...50 mm 1.57...1.97 in. from the left rim ButtonOverview Safety-Related Communication Communication via switchesCommunication Following scheme shows a SafeEthernet networking example HIMatrix F3AIOConnector pairs and cable distances Following is a Ethernet cable connection diagramNumber Maximum cable distanceEquipment Description LEDs LED Description Following table describes behaviors of the LEDsColor Status Meaning LED Ethernet Wiring WiringInterface ElementsSwitches RJ45 ConnectorClass D capacity are required RecommendedIP Addressing and System ID DescriptionBit numbers e.g SafeEthernet 33003405 07/2007 Parameters OperationEthernet InterfacesUsed Network Ports for Ethernet Communication Connections for SafeEthernet/ Networking ExamplesUDP ports and usage TCP ports and usageFor the next higher level and relies on the next lower level OSI modelNumber Layer Data Description Following table describes the seven OSI layers bottom-topOperating Conditions ClimaticConditions Mechanical EMC ConditionsFollowing tables Equipment Description Mechanical Data Power Supply Connectors Technical CharacteristicsPower Supply Connectors Signal Line ConnectorsStripping Length and Torque Supply voltage Relay OutputsAdditional Items List of AdditionalItems Equipment Description Equipment Description Appendix contains the following chapters AppendicesAppendix? Chapter Chapter NameAppendices Connection Diagrams, Examples Application, and Error Codes System signal Meaning Error CodesBrief description of the functional devices SafeEthernet Protocol Ethernet Wiring Example Wiring ExamplesElements of the network NetworkingBrief description of the functional devices Modbus serial ElementCommunication Settings Configuration of Ethernet InterfacesFor setting the communication parameters proceed as follows Flow-Control Mode list, select AutonegKonfiguration/Abl-Mode/HIMatrix F35/OM Parameters of a port configurationParameter Description Following table contains the parameter descriptionsBrief description of the functional devices Glossary Fault tolerance time Functional block diagramField bus See FTTOSI Model Open system interconnection model Object linking and embeddingProtective extra low voltage Programmable electronic systemSequential function chart Safety extra low voltageSafety integrity level according to IEC System-rack-slotIndex Index