Schneider Electric XPSMF2DO801 manual Relay Outputs, Supply voltage

Page 61

 

 

Equipment Description

 

Relay Outputs

 

 

 

 

 

Relay Types per Channel

2 Safety relays with positively guided contacts,

 

 

1 standard type relay

 

 

 

 

Number of Outputs

8 Potential-free NO contacts in diversity

 

 

 

 

Output Voltage

2 VDC

 

 

 

 

Switching Voltage

5 V, 250 VAC / 250 VDC

 

 

 

 

Switching Current

internally fused with 3.15 A

 

 

breaking capacity 100 A

 

 

 

 

Switching Capacity AC

UL:

 

 

250 VAC @ 6 A GP

 

 

TÜV:

 

 

max. 250 VA, cos ϕ ≥ 0.5, at max. 250 VAC

 

 

max. 625 VA, cos ϕ = 1

 

 

 

 

Switching Capacity DC (non-

UL: 24 VDC @ 1 A at resistive load

 

Inductive)

TÜV:

 

 

up to 30 VDC: Max. 90 W (3.15 A)

 

 

up to 70 VDC: Max. 22 W (0.315 A)

 

 

up to 127 VDC: Max. 25 W (0.25 A)

 

 

up to 250 VDC: Max. 40 W (0.16 A)

 

 

(external fusing adapted)

 

 

 

 

Contact Material

silver alloy

 

 

 

 

Switching Time

approx. 30 mS

 

 

 

 

Reset Time

approx. 10 mS

 

 

 

 

Bounce Time

approx. 15 mS

 

 

 

 

Service Life Mechanical and

3 x 106 switching cycles

 

Electrical

2.5 x 105 switching cycles with resistive full load and

 

 

0.1 switching cycles per second

 

 

 

 

 

 

 

 

 

 

 

 

Supply Voltage The XPSMF2DO801 safety remote output device is a single voltage system. The required operating voltage is defined as follows in accordance with IEC/EN 61131-2.

Supply voltage

Nominal value

24 VDC, -15...+20%

 

 

Max. permissible function

18.5 to 30.2 VDC (including ripple)

limits in continuous operation

 

 

 

Max. peak value

35 VDC for 0.1 s

 

 

Permissible ripple

w < 5% as r.m.s. value wss < 15% as value peak-to-peak

 

 

Reference potential

L - (negative pole)

 

Earthing the reference potential is permitted.

 

 

33003405 07/2007

61

Image 61
Contents 07/2007 XPSMF2DO801 Remote Output Module Hardware ManualPage Table of Contents At a Glance AppendicesProcedure Safety InformationImportant Information Safety Information At a Glance About the Book33003405 07/2007 Overview Whats in this Chapter? Overview XPSMF2DO801Topic Representation IntroductionFront View ModuleDimensions Remote output module DimensionsSide View Procedure InstallationIntroduction Step ActionHIMatrix 100 Compact device Cable duct Spacer Length of the required spacer is calculated as follows Installation with spacers= H 40 mm / 1.57 = length of the spacer = height of the cable ductHIMatrix F31 Heat Case installation Calculation of a m2 1m2=10.76ft2 Internal HousingConvection Variable DescriptionTemperature range Temperature state Temperature State/OperatingOverview Application and Function Initial Operation XPSMF2DO801 safety remote output moduleOverview StageApplication Function Terminal No Designation Function relay output Application and Function Disconnection CableFollowing will occur SystemLarge System Reconfiguration Power Supply InterruptionVoltage level Reaction of the controller StepSHORT-CIRCUIT Condition Short-Circuit Characteristics Output ChannelsModules Offline Proof Test Offline Proof-Test Periodic Proof TestingExecution Offline ProofOutput module Equipment DescriptionWhats in this Chapter?XPSMF2DO801 safety remote output module Housing ElementsElements of the front panel Top View Following image shows the elements of the top panel Back Panel Following image shows elements of the back panel Using Reset Reset ButtonHousing, about 40...50 mm 1.57...1.97 in. from the left rim ButtonCommunication via switches Overview Safety-Related CommunicationCommunication Following scheme shows a SafeEthernet networking example HIMatrix F3AIOConnector pairs and cable distances Following is a Ethernet cable connection diagramNumber Maximum cable distanceEquipment Description LEDs Following table describes behaviors of the LEDs LED DescriptionColor Status Meaning LED Ethernet Wiring WiringInterface ElementsSwitches RJ45 ConnectorClass D capacity are required RecommendedDescription IP Addressing and System IDBit numbers e.g SafeEthernet 33003405 07/2007 Parameters OperationEthernet InterfacesUsed Network Ports for Ethernet Communication Connections for SafeEthernet/ Networking ExamplesUDP ports and usage TCP ports and usageFor the next higher level and relies on the next lower level OSI modelNumber Layer Data Description Following table describes the seven OSI layers bottom-topClimatic Operating ConditionsConditions EMC Conditions MechanicalFollowing tables Equipment Description Mechanical Data Power Supply Connectors Technical CharacteristicsPower Supply Connectors Signal Line ConnectorsStripping Length and Torque Supply voltage Relay OutputsList of Additional Additional ItemsItems Equipment Description Equipment Description Appendix contains the following chapters AppendicesAppendix? Chapter Chapter NameAppendices Connection Diagrams, Examples Application, and Error Codes System signal Meaning Error CodesBrief description of the functional devices SafeEthernet Protocol Ethernet Wiring Example Wiring ExamplesElements of the network NetworkingBrief description of the functional devices Modbus serial ElementCommunication Settings Configuration of Ethernet InterfacesFor setting the communication parameters proceed as follows Flow-Control Mode list, select AutonegKonfiguration/Abl-Mode/HIMatrix F35/OM Parameters of a port configurationParameter Description Following table contains the parameter descriptionsBrief description of the functional devices Glossary Fault tolerance time Functional block diagramField bus See FTTOSI Model Open system interconnection model Object linking and embeddingProtective extra low voltage Programmable electronic systemSequential function chart Safety extra low voltageSafety integrity level according to IEC System-rack-slotIndex Index