| Equipment Description |
| Relay Outputs |
|
|
|
|
| Relay Types per Channel | 2 Safety relays with positively guided contacts, |
|
| 1 standard type relay |
|
|
|
| Number of Outputs | 8 |
|
|
|
| Output Voltage | 2 VDC |
|
|
|
| Switching Voltage | ≥ 5 V, ≤ 250 VAC / 250 VDC |
|
|
|
| Switching Current | internally fused with 3.15 A |
|
| breaking capacity 100 A |
|
|
|
| Switching Capacity AC | UL: |
|
| 250 VAC @ 6 A GP |
|
| TÜV: |
|
| max. 250 VA, cos ϕ ≥ 0.5, at max. 250 VAC |
|
| max. 625 VA, cos ϕ = 1 |
|
|
|
| Switching Capacity DC (non- | UL: 24 VDC @ 1 A at resistive load |
| Inductive) | TÜV: |
|
| up to 30 VDC: Max. 90 W (3.15 A) |
|
| up to 70 VDC: Max. 22 W (0.315 A) |
|
| up to 127 VDC: Max. 25 W (0.25 A) |
|
| up to 250 VDC: Max. 40 W (0.16 A) |
|
| (external fusing adapted) |
|
|
|
| Contact Material | silver alloy |
|
|
|
| Switching Time | approx. 30 mS |
|
|
|
| Reset Time | approx. 10 mS |
|
|
|
| Bounce Time | approx. 15 mS |
|
|
|
| Service Life Mechanical and | ≥ 3 x 106 switching cycles |
| Electrical | ≥ 2.5 x 105 switching cycles with resistive full load and |
|
| ≤ 0.1 switching cycles per second |
|
|
|
|
|
|
|
|
|
|
|
|
Supply Voltage The XPSMF2DO801 safety remote output device is a single voltage system. The required operating voltage is defined as follows in accordance with IEC/EN
Supply voltage
Nominal value | 24 VDC, |
|
|
Max. permissible function | 18.5 to 30.2 VDC (including ripple) |
limits in continuous operation |
|
|
|
Max. peak value | 35 VDC for 0.1 s |
|
|
Permissible ripple | w < 5% as r.m.s. value wss < 15% as value |
|
|
Reference potential | L - (negative pole) |
| Earthing the reference potential is permitted. |
|
|
33003405 07/2007 | 61 |