Page 39

 

Equipment Description

 

Reset Button

 

 

 

 

 

 

 

 

 

 

 

Overview

The device is equipped with a reset button. The reset button is used if the PC

 

 

connection password is lost.

 

 

 

 

 

 

 

 

 

 

Using Reset

You can access the pushbutton through a small round opening on the upper side of

 

Button

the housing, about 40...50 mm (1.57...1.97 in.) from the left rim.

 

 

Use the button only while you reboot the device and keep the button pressed for at

 

 

least 20 s. Pushing the reset button while the device is running produces no result.

 

 

 

 

 

 

 

 

 

 

Effect

When you push the Reset button,

 

 

￿ all accounts are deactivated (except the default Administrator account

 

 

without password) and

 

 

￿ IP addresses and system ID (SRS) are set to default values.

 

 

 

 

 

Note: After activation of the reset button, values are modified and remain valid until

 

 

the next reboot. After the next reboot the previous values are restored. You can

 

 

enter new information, if necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

33003405 07/2007

39

Image 39
Contents 07/2007 XPSMF2DO801 Remote Output Module Hardware ManualPage Table of Contents At a Glance AppendicesSafety Information ProcedureImportant Information Safety Information At a Glance About the Book33003405 07/2007 Overview XPSMF2DO801 Overview Whats in this Chapter?Topic Module IntroductionRepresentation Front ViewDimensions Remote output module DimensionsSide View Step Action InstallationProcedure IntroductionHIMatrix 100 Compact device Cable duct Spacer = length of the spacer = height of the cable duct Installation with spacersLength of the required spacer is calculated as follows = H 40 mm / 1.57HIMatrix F31 Heat Case installation Calculation of a m2 1m2=10.76ft2 Variable Description HousingInternal ConvectionTemperature range Temperature state Temperature State/OperatingOverview Application and Function Stage XPSMF2DO801 safety remote output moduleInitial Operation OverviewApplication Function Terminal No Designation Function relay output Application and Function System CableDisconnection Following will occurStep Power Supply InterruptionLarge System Reconfiguration Voltage level Reaction of the controllerSHORT-CIRCUIT Condition Short-Circuit Characteristics Output ChannelsModules Offline Proof Test Offline Proof Periodic Proof TestingOffline Proof-Test ExecutionChapter? Equipment DescriptionOutput module Whats in thisHousing Elements XPSMF2DO801 safety remote output moduleElements of the front panel Top View Following image shows the elements of the top panel Back Panel Following image shows elements of the back panel Button Reset ButtonUsing Reset Housing, about 40...50 mm 1.57...1.97 in. from the left rimOverview Safety-Related Communication Communication via switchesCommunication Following scheme shows a SafeEthernet networking example HIMatrix F3AIOMaximum cable distance Following is a Ethernet cable connection diagramConnector pairs and cable distances NumberEquipment Description LEDs LED Description Following table describes behaviors of the LEDsColor Status Meaning LED Elements WiringEthernet Wiring InterfaceRecommended RJ45 ConnectorSwitches Class D capacity are requiredIP Addressing and System ID DescriptionBit numbers e.g SafeEthernet 33003405 07/2007 Interfaces OperationParameters EthernetTCP ports and usage Connections for SafeEthernet/ Networking ExamplesUsed Network Ports for Ethernet Communication UDP ports and usageFor the next higher level and relies on the next lower level OSI modelNumber Layer Data Description Following table describes the seven OSI layers bottom-topOperating Conditions ClimaticConditions Mechanical EMC ConditionsFollowing tables Equipment Description Signal Line Connectors Technical CharacteristicsMechanical Data Power Supply Connectors Power Supply ConnectorsStripping Length and Torque Supply voltage Relay OutputsAdditional Items List of AdditionalItems Equipment Description Equipment Description Chapter Chapter Name AppendicesAppendix contains the following chapters Appendix?Appendices Connection Diagrams, Examples Application, and Error Codes System signal Meaning Error CodesBrief description of the functional devices Networking Wiring ExamplesSafeEthernet Protocol Ethernet Wiring Example Elements of the networkBrief description of the functional devices Modbus serial ElementFlow-Control Mode list, select Autoneg Configuration of Ethernet InterfacesCommunication Settings For setting the communication parameters proceed as followsKonfiguration/Abl-Mode/HIMatrix F35/OM Parameters of a port configurationParameter Description Following table contains the parameter descriptionsBrief description of the functional devices Glossary See FTT Functional block diagramFault tolerance time Field busProgrammable electronic system Object linking and embeddingOSI Model Open system interconnection model Protective extra low voltageSystem-rack-slot Safety extra low voltageSequential function chart Safety integrity level according to IECIndex Index