Schneider Electric XPSMF2DO801 manual Error Codes, System signal Meaning

Page 68

Brief description of the functional devices

Error Codes

Description of

The error codes listed in this section appear in XPSMFWIN programming

Error Codes

environment.

 

 

The following table describes error codes of relay outputs:

 

 

 

 

 

System signal

 

R/W

Meaning

 

 

 

 

 

Module.SRS [UDINT]

 

R

slot number (System-Rack-Slot)

 

 

 

 

Module.Type [UINT]

 

R

type of module, setpoint: 0x003C [60dez]

 

 

 

Module.Error Code [WORD]

R

error codes of the module

 

 

 

 

 

 

 

 

0x0000

I/O processing, may be faulty, see further error codes

 

 

 

0x0001

no I/O processing (CPU not in RUN)

 

 

 

0x0002

no I/O processing during start-up tests

 

 

 

0x0004

manufacturer interface in operation

 

 

 

0x0010

no I/O processing: incorrect configuration

 

 

 

0x0020

no I/O processing: error rate exceeded

 

 

 

0x0040

no I/O processing: configured module not inserted

 

 

 

0x0080

 

 

 

 

 

 

DO.Error Code [WORD]

 

R

error codes of all digital outputs

 

 

 

 

 

 

 

 

0x0001

module error

 

 

 

0x0002

MEZ test, safety switch 1 failed

 

 

 

0x0004

MEZ test, safety switch 2 failed

 

 

 

0x0008

FTZ test of test pattern failed

 

 

 

0x0010

MEZ test of readback channels failed

 

 

 

0x0020

MEZ test, active disconnection failed

 

 

 

0x0040

error with initialization: relays

 

 

 

0x0080

FTZ test: error of relay voltage

 

 

 

0x0100

FTZ test of CS (chip select) signals failed

 

 

 

0x0400

FTZ test: 1. temperature threshold exceeded

 

 

 

0x0800

FTZ test: 2. temperature threshold exceeded

 

 

 

0x1000

MEZ test: status of safety switch 1

 

 

 

0x2000

MEZ test: status of safety switches

 

 

 

0x4000

MEZ test: active disconection by watchdog failed

 

 

 

 

 

68

33003405 07/2007

Image 68
Contents XPSMF2DO801 Remote Output Module Hardware Manual 07/2007Page Table of Contents Appendices At a GlanceImportant Information Safety InformationProcedure Safety Information About the Book At a Glance33003405 07/2007 Topic Overview XPSMF2DO801Overview Whats in this Chapter? Introduction RepresentationFront View ModuleDimensions Dimensions Remote output moduleSide View Installation ProcedureIntroduction Step ActionHIMatrix 100 Compact device Cable duct Spacer Installation with spacers Length of the required spacer is calculated as follows= H 40 mm / 1.57 = length of the spacer = height of the cable ductHIMatrix F31 Heat Case installation Calculation of a m2 1m2=10.76ft2 Housing InternalConvection Variable DescriptionTemperature State/Operating Temperature range Temperature stateOverview Application and Function XPSMF2DO801 safety remote output module Initial OperationOverview StageApplication Function Terminal No Designation Function relay output Application and Function Cable DisconnectionFollowing will occur SystemPower Supply Interruption Large System ReconfigurationVoltage level Reaction of the controller StepShort-Circuit Characteristics Output Channels SHORT-CIRCUIT ConditionModules Offline Proof Test Periodic Proof Testing Offline Proof-TestExecution Offline ProofEquipment Description Output moduleWhats in this Chapter?Elements of the front panel Housing ElementsXPSMF2DO801 safety remote output module Top View Following image shows the elements of the top panel Back Panel Following image shows elements of the back panel Reset Button Using ResetHousing, about 40...50 mm 1.57...1.97 in. from the left rim ButtonCommunication Overview Safety-Related CommunicationCommunication via switches HIMatrix F3AIO Following scheme shows a SafeEthernet networking exampleFollowing is a Ethernet cable connection diagram Connector pairs and cable distancesNumber Maximum cable distanceEquipment Description LEDs Color Status Meaning LED DescriptionFollowing table describes behaviors of the LEDs LED Wiring Ethernet WiringInterface ElementsRJ45 Connector SwitchesClass D capacity are required RecommendedBit numbers e.g IP Addressing and System IDDescription SafeEthernet 33003405 07/2007 Operation ParametersEthernet InterfacesConnections for SafeEthernet/ Networking Examples Used Network Ports for Ethernet CommunicationUDP ports and usage TCP ports and usageOSI model For the next higher level and relies on the next lower levelFollowing table describes the seven OSI layers bottom-top Number Layer Data DescriptionConditions Operating ConditionsClimatic Following tables MechanicalEMC Conditions Equipment Description Technical Characteristics Mechanical Data Power Supply ConnectorsPower Supply Connectors Signal Line ConnectorsStripping Length and Torque Relay Outputs Supply voltageItems Additional ItemsList of Additional Equipment Description Equipment Description Appendices Appendix contains the following chaptersAppendix? Chapter Chapter NameAppendices Connection Diagrams, Examples Application, and Error Codes Error Codes System signal MeaningBrief description of the functional devices Wiring Examples SafeEthernet Protocol Ethernet Wiring ExampleElements of the network NetworkingBrief description of the functional devices Element Modbus serialConfiguration of Ethernet Interfaces Communication SettingsFor setting the communication parameters proceed as follows Flow-Control Mode list, select AutonegParameters of a port configuration Konfiguration/Abl-Mode/HIMatrix F35/OMFollowing table contains the parameter descriptions Parameter DescriptionBrief description of the functional devices Glossary Functional block diagram Fault tolerance timeField bus See FTTObject linking and embedding OSI Model Open system interconnection modelProtective extra low voltage Programmable electronic systemSafety extra low voltage Sequential function chartSafety integrity level according to IEC System-rack-slotIndex Index