Garmin EDP70 manual Contactor 24/36kVA Ratings

Page 13

Reserve Supply

AC Supply

S3

Maintenance By-pass

S2

 

S1

S4

Battery

24/36kVA Ratings

Contactor

S3

Reserve Supply S2

S1

AC Supply

Maintenance By-pass

S5

480Y/277V

 

S4

208Y/120V

Battery

Contactor 50/80kVA Ratings

Figure 5 – Re-establishing the Utility Supply

When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will result in reduced standby times.

S3

Reserve Supply

S2

S1

AC Supply

Maintenance By-pass

S4

Battery

Contactor 24/36kVA Ratings

 

S3

Reserve Supply

S2

 

S1

AC Supply

 

 

Maintenance By-pass

 

S5

 

480Y/277V

 

S4

 

208Y/120V

Battery

50/80kVA Ratings

Contactor

Figure 6 – Transferring the Load onto the Reserve Supply

Transfer onto the reserve line is caused by two conditions:

a)inverter stop

b)overload

In both instances the load is transferred onto the reserve without interruption. If the overload is temporary, the system will re-transfer from reserve to inverter as soon as the it ceases. This allows for the initial start-up of loads with high or excessive switch-on currents.

MI00/10056 rev. 8 — 05/2006-- page 13

Image 13
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Emergency Procedure Electrical PrecautionsElectric Shock Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 36kVA Standard Configuration 24kVA Standard Configuration36kVA 480V/208V Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Fuse Access PlateCable EntryPoints Connection40.16 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Connection Uninterruptible Power System No Unauthorized Operation#$# % # #% + ,+% M10 AWGNest Stationary Tool Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations RAU Female FrontRear U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS2 QS1 QS4Terminal board compartment 40 --MI00/10056 rev -05/2006 Rear QS1 QS2 QS3 QS4 QS5Signal connections Emergency Power Off Controls Right Control Maintenance Bypass SHUT-DOWN Installing the EPOMimic Silencing Audible AlarmLiquid Crystal Display Inverter Alarms No Alarms Active RECT/BATT Alarms No Alarms ActiveLOAD/RES Alarms No Alarms Active Display Page HeadingsSelected Language English Battery Test WeeklyPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Inverter F xx.x Hz Xxx V B xxx V C xxx Vdc xxx V Ib xxxx aInverter F xx.x Hz AB xxx V BC xxx V CA xxx InverterLoad Main page Heading Alarms Message Condition Abnormal operating mode messagesSystem Alarm Overload Battery DischargingStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Matrix Power HistoryBattery Autonomy Test Battery TestResetting data loss manually System normal message11.1 AS400 11.2 RS232 Safety 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle EDP70 PLUS/24/18/12 Internal Battery Shelves13.4 EDP70 Plus above 24KVA Battery Cubicle 13.3 EDP70 Plus above 24KVA Battery Installation/Start-upEDP70 Plus System LOG