Garmin EDP70 manual MI00/10056 rev -05/2006

Page 40

S5 = RESERVE OUTPUT switch

S4 = INVERTER OUTPUT Breaker

S3 = BY PASS switch

S2 = Equipment RESERVE switch

S1 = Equipment ON/OFF Breaker

Output, Input, Reserve

and External Battery Terminals

Access plate

Figure 25 – 50/80kVA: Connections

Access to the terminals for electrical connections is as follows:

a)Remove front panel see Figure 22.

b)Remove the terminal board compartment panel by unscrewing the fixing screws at the front.

e)This exposes the electrical terminal rail, see Figure 23

f)Remove the screws securing the access plate.

e)Push the interconnection cables up through the access plate.

f)Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with the correct size lugs and connected on the bottom side terminals as marked.

g)Install or start-up batteries see section 13.3 and 13.4.

h)Replace and tighten the terminal securing screws fully clockwise and refit the access plate.

i)Replace the terminal board compartment panel and the front cover.

OBSERVE POLARITIES AND ORIENTATIONS.

See Remote Alarms and Computer Interface for connections to these facilities.

page 40 --MI00/10056 rev. 8 —05/2006

Image 40
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Electrical Precautions Emergency ProcedureElectric Shock Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 36kVA Standard Configuration 24kVA Standard Configuration36kVA 480V/208V Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Access Plate FuseCable EntryConnection Points40.16 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Uninterruptible Power System No Unauthorized Operation Connection#$# % # #% + ,+% AWG M10Nest Stationary Tool Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations Front RAU FemaleRear U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS1 QS4 QS2Terminal board compartment 40 --MI00/10056 rev -05/2006 QS1 QS2 QS3 QS4 QS5 RearSignal connections Emergency Power Off Controls Right Control Maintenance Bypass Installing the EPO SHUT-DOWNMimic Silencing Audible AlarmLiquid Crystal Display RECT/BATT Alarms No Alarms Active Inverter Alarms No Alarms ActiveLOAD/RES Alarms No Alarms Active Display Page HeadingsBattery Test Weekly Selected Language EnglishPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Vdc xxx V Ib xxxx a Inverter F xx.x Hz Xxx V B xxx V C xxxInverter F xx.x Hz AB xxx V BC xxx V CA xxx InverterLoad Main page Heading Alarms Message Condition Abnormal operating mode messagesSystem Alarm Overload Battery DischargingStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Power History MatrixBattery Test Battery Autonomy TestResetting data loss manually System normal message11.1 AS400 11.2 RS232 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up SafetyEDP70 PLUS/24/18/12 Internal Battery Shelves 13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle13.3 EDP70 Plus above 24KVA Battery Installation/Start-up 13.4 EDP70 Plus above 24KVA Battery CubicleEDP70 Plus System LOG