7.0START UP

1.Switch on the AC reserve and the main AC Utility supply to the UPS.

2.Turn on the Utility supply Input, Reserve Input (if fitted) and UPS Output switches located behind the front panel, see figure 18 for 24kVA, figure 21 for 36kVA or figure 24 for 50/80kVA.

3.Replace the front panel.

4.Press the CANCEL AUDIBLE ALARM switch (see section 6.2)

5.Initially, all the green indicators will flash on the display mimic. After about 30 seconds the supply and battery indicators should stop flashing.

6.Press the Inverter On push button (I).

7.The inverter should now start and after a delay of approximately 30 seconds the message ‘SYSTEM NORMAL’, in English, will appear on the liquid crystal display.

8. Select the required language by pressing page right control

until the ‘SELECT LANGUAGE’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

message appears on the liquid crystal display. Press the page down control

 

 

until the required

 

 

 

once more confirm the language selection.

 

 

language is selected. Press the page right control

 

Thereafter, all messages will appear in the selected language.

 

 

 

 

 

8.0MAINTENANCE BYPASS

The EDP70 PLUS UPS is equipped with Manual Maintenance Bypass systems. If a unit requires servicing, the Manual Maintenance Bypass allows the load to be connected directly to the AC supply so that the unit may be serviced in safety. The following instructions must be followed:

1.Ensure that ‘SYSTEM NORMAL’ is displayed on the LCD. (Note: If ‘SYSTEM NORMAL’ is not displayed check that the inverter is not ‘OUT OF SYNC’, see section 10.7. Turning the inverter off under this fault condition will interrupt the load supply.)

2.Turn off the inverter by pressing the inverter shutdown button for more than 2 seconds

3.Turn the Maintenance Bypass Switch (located behind front panel, see figure 18, 21 or 24) to ON.

4.Turn off the Primary Input, Reserve Input and UPS Output Switches, see figure 18, 21 or 24.

THE LOAD IS NOW SUPPLIED DIRECTLY FROM THE AC UTILITY SUPPLY AND IS NO LONGER PROTECTED BY THE UPS

CAUTION: Some components in the UPS will retain a static voltage even after the switches have been opened. Also, on the 50/80kVA ratings, the isolating transformer and the relative cooling fans are still supplied from the Bypass.

To return to the normal operating mode, follow the above procedure in reverse.

Note: The EDP70 PLUS UPS must not be left operating with the Maintenance Bypass Switch in the ON position.

MI00/10056 rev. 8 — 05/2006-- page 45

Image 45
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Emergency Procedure Electrical PrecautionsElectric Shock Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 24kVA Standard Configuration 36kVA Standard Configuration36kVA 480V/208V Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Fuse Access PlateCable EntryPoints Connection40.16 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Connection Uninterruptible Power System No Unauthorized Operation#$# % # #% + ,+% M10 AWGNest Stationary Tool Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations RAU Female FrontRear U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS2 QS1 QS4Terminal board compartment 40 --MI00/10056 rev -05/2006 Rear QS1 QS2 QS3 QS4 QS5Signal connections Emergency Power Off Controls Right Control Maintenance Bypass SHUT-DOWN Installing the EPOSilencing Audible Alarm MimicLiquid Crystal Display Inverter Alarms No Alarms Active RECT/BATT Alarms No Alarms ActiveLOAD/RES Alarms No Alarms Active Display Page HeadingsSelected Language English Battery Test WeeklyPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Inverter F xx.x Hz Xxx V B xxx V C xxx Vdc xxx V Ib xxxx aInverter F xx.x Hz AB xxx V BC xxx V CA xxx InverterLoad Abnormal operating mode messages Main page Heading Alarms Message ConditionSystem Alarm Battery Discharging OverloadStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Matrix Power HistoryBattery Autonomy Test Battery TestResetting data loss manually System normal message11.1 AS400 11.2 RS232 Safety 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle EDP70 PLUS/24/18/12 Internal Battery Shelves13.4 EDP70 Plus above 24KVA Battery Cubicle 13.3 EDP70 Plus above 24KVA Battery Installation/Start-upEDP70 Plus System LOG