Garmin EDP70 manual Recommended wire sizes

Page 27

Recommended wire sizes

1)It is recommended that the external cables and protection be selected for the highest rated unit of the model in use.

2)Reserve (or primary) input and output Neutral cable size should be greater than that of the line cables in order to be able to supply non-linear loads having a Crest Factor of up to 3:1 (i.e. where neutral current = 1.7 x line current).

If non-linear loads are not to be supplied from the Installation, the Neutral can be of the same size as the load cable.

3)Recommended AC input overcurrent protection represents 125% of nominal full load

current (continuous) plus the short duration input current (non-continuous) for battery re- charging per NEC 215.2.

4)UPS output cables should be run in separate conduits from input cables.

5)Grounding conductors are sized per NEC 250.122.

6)Cable sizes are based upon NEC.

Refer to local codes applying to your installation prior to choosing appropriate cable size.

Refer to UPS ampacity table on following page.

MI00/10056 rev. 8 — 05/2006-- page 27

Image 27
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Injuries Caused by Contact with Corrosive Liquids Electrical PrecautionsEmergency Procedure Electric ShockContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 24kVA Standard Configuration 36kVA Standard Configuration36kVA 480V/208V Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Entry Access PlateFuse Cable32.68 ConnectionPoints 40.16BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Connection Uninterruptible Power System No Unauthorized Operation#$# % # #% + ,+% Indentor Moveable AWGM10 Nest Stationary ToolS2 = Equipment Reserve Switch Observe Polarities and Orientations U1V1W1N PE U V W N U2V2W2 N FrontRAU Female Rear36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS2 QS1 QS4Terminal board compartment 40 --MI00/10056 rev -05/2006 Rear QS1 QS2 QS3 QS4 QS5Signal connections Emergency Power Off Controls Right Control Maintenance Bypass SHUT-DOWN Installing the EPOSilencing Audible Alarm MimicLiquid Crystal Display Display Page Headings RECT/BATT Alarms No Alarms ActiveInverter Alarms No Alarms Active LOAD/RES Alarms No Alarms ActiveSelected Language English Battery Test WeeklyPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Inverter Vdc xxx V Ib xxxx aInverter F xx.x Hz Xxx V B xxx V C xxx Inverter F xx.x Hz AB xxx V BC xxx V CA xxxLoad Abnormal operating mode messages Main page Heading Alarms Message ConditionSystem Alarm Battery Discharging OverloadStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Matrix Power HistorySystem normal message Battery TestBattery Autonomy Test Resetting data loss manually11.1 AS400 11.2 RS232 Safety 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle EDP70 PLUS/24/18/12 Internal Battery Shelves13.4 EDP70 Plus above 24KVA Battery Cubicle 13.3 EDP70 Plus above 24KVA Battery Installation/Start-upEDP70 Plus System LOG