Garmin EDP70 manual Storage

Page 16

3.0STORAGE

If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life. The date the battery was last recharged and the date the battery is due for its next recharge are both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge date.

When the EDP70 PLUS is due to be recharged, refer to the Installation instructions and connect the EDP70 PLUS UPS to a temporary AC supply. The battery MUST be recharged for at least 24 hours every 3 months.

4.0INSTALLATION

4.1Mechanical characteristics

-

Ambient temperature

 

 

18°F[-10°C] to 104°F [+40°C ]

 

- Relative Humidity (w/out condensing @ 68°F[20°C])

< 90%

 

 

- Max altitude (w/out derating)

 

3300 feet [1000 m] above sea-level

 

- Protection degree (panel fitted)

 

 

 

 

 

 

-

Input cables

 

 

 

bottom

 

-

Air inlet

 

 

 

 

bottom

 

-

Air outlet

 

 

 

 

rear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS model

 

 

 

Description

u.m.

24

36

 

 

50

80

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

width

In

28-.5 [700]

27.5 [700]

 

 

35.4 [900]

35.4 [900]

 

 

 

depth

[mm]

28.7 [730]

28.7 [730]

 

 

28.7 [730]

28.7 [730]

 

 

 

height

 

56 [1420]

56 [1420]

 

 

63 [1600]

63 [1600]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

w/out cells

Lbs

880 [400]

1300 [590]

 

 

1342 [610]

1800 [818]

 

 

Weight

25 Ah cells

[kg]

1342 [610]

n.a.

 

 

n.a.

n.a.

 

 

(UPS +

30 Ah cells

 

1456 [662]

n.a.

 

 

 

 

 

 

 

n.a.

n.a.

 

 

Battery)

35 Ah cells

 

1526 [694]

n.a.

 

 

 

 

 

 

 

n.a.

n.a.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor Area

In2[m2]

789 [0.511]

789 [0.511]

 

1019 [0.657]

1019 [0.657]

 

 

Floor

w/out cells

Lbs/in2

1.12 [782]

1.65 [1155]

 

1.32 [930]

1.77 [1245]

 

 

Loading

25 Ah cells

[kg/m2]

1.70 [1194]

n.a.

 

 

n.a.

n.a.

 

 

(UPS +

30 Ah cells

 

1.85 [1296]

n.a.

 

 

 

 

 

 

 

n.a.

n.a.

 

 

Battery)

35 Ah cells

 

1.93 [1358]

n.a.

 

 

 

 

 

 

 

n.a.

n.a.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air-Flow

cfm

235

647

 

 

1165

1553

 

 

 

 

[mc/h]

[400]

[1100]

 

 

[1980]

[2640]

 

 

 

 

 

 

 

 

 

 

 

 

Acoustic Noise

dBA

52

55

 

 

55

62

 

 

100% Linear Load

 

 

 

 

 

 

 

Notes:

1)

n.a. = not applicable

 

 

 

 

 

 

2)Longer autonomies, and battery for EDP above 20 kVA are available with external battery cubicles.

page 16 --MI00/10056 rev. 8 —05/2006

Image 16
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Electrical Precautions Emergency ProcedureElectric Shock Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 36kVA Standard Configuration 24kVA Standard Configuration36kVA 480V/208V Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Access Plate FuseCable EntryConnection Points40.16 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Uninterruptible Power System No Unauthorized Operation Connection#$# % # #% + ,+% AWG M10Nest Stationary Tool Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations Front RAU FemaleRear U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS1 QS4 QS2Terminal board compartment 40 --MI00/10056 rev -05/2006 QS1 QS2 QS3 QS4 QS5 RearSignal connections Emergency Power Off Controls Right Control Maintenance Bypass Installing the EPO SHUT-DOWNMimic Silencing Audible AlarmLiquid Crystal Display RECT/BATT Alarms No Alarms Active Inverter Alarms No Alarms ActiveLOAD/RES Alarms No Alarms Active Display Page HeadingsBattery Test Weekly Selected Language EnglishPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Vdc xxx V Ib xxxx a Inverter F xx.x Hz Xxx V B xxx V C xxxInverter F xx.x Hz AB xxx V BC xxx V CA xxx InverterLoad Main page Heading Alarms Message Condition Abnormal operating mode messagesSystem Alarm Overload Battery DischargingStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Power History MatrixBattery Test Battery Autonomy TestResetting data loss manually System normal message11.1 AS400 11.2 RS232 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up SafetyEDP70 PLUS/24/18/12 Internal Battery Shelves 13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle13.3 EDP70 Plus above 24KVA Battery Installation/Start-up 13.4 EDP70 Plus above 24KVA Battery CubicleEDP70 Plus System LOG