10.7Battery Test
The EDP70 PLUS has an automatic battery control function which checks the condition of the battery periodically without affecting the output in any way. While this test is being carried out, the message »TESTING BATTERY» will appear. This test can also be activated manually. Return to the main title page so that ‘SYSTEM NORMAL’ is displayed.
UPS xx KVA
SYSTEM NORMAL
system normal message
PRESS SIMULTANEOUSLY
(The test is disabled if the BATTERY TEST selected is NONE)
UPS xx KVA
TESTING BATTERY
The battery test is underway and takes approx. 1 minute. If the test is completed without giving off any alarm, then the system returns to normal operating mode; otherwise, the alarm message »BATTERY FAULT» is displayed.
10.8Battery Autonomy Test
The EDP70 PLUS has a battery autonomy test which disables the rectifier manually.
To carry out this test, return to the main title page so that ‘SYSTEM NORMAL’ is displayed.
UPS xx KVA
SYSTEM NORMAL
system normal message
PRESS SIMULTANEOUSLY and keep pressed for 2 seconds
(The test is diabled if the BATTERY TEST selected is NONE)
UPS xx KVA
TESTING AUTONOMY
The battery starts to discharge completely thereby allowing the autonomy to be checked. Once the battery has been discharged, the test comes to an end automatically and the rectifier restarts.
To interrupt BATTERY autonomy Test, at any time: PRESS SIMULTANEOUSLY |
| and | keep pressed |
| |||
for 2 seconds |
|
|
|
10.9Resetting data loss manually
If the message »NOT CALIBRATED» appears on the main title page, this means that data (language and total number of mains failures) which do not directly affect the functioning of the machine have been lost. Despite this, data has still been lost and the intervention of a qualified technician is required.It is, nevertheless, possible to reset the normal operating mode by selecting the language desired as described under sect. 7.0.