10.7Battery Test

The EDP70 PLUS has an automatic battery control function which checks the condition of the battery periodically without affecting the output in any way. While this test is being carried out, the message »TESTING BATTERY» will appear. This test can also be activated manually. Return to the main title page so that ‘SYSTEM NORMAL’ is displayed.

UPS xx KVA

SYSTEM NORMAL

system normal message

PRESS SIMULTANEOUSLY

(The test is disabled if the BATTERY TEST selected is NONE)

UPS xx KVA

TESTING BATTERY

The battery test is underway and takes approx. 1 minute. If the test is completed without giving off any alarm, then the system returns to normal operating mode; otherwise, the alarm message »BATTERY FAULT» is displayed.

10.8Battery Autonomy Test

The EDP70 PLUS has a battery autonomy test which disables the rectifier manually.

To carry out this test, return to the main title page so that ‘SYSTEM NORMAL’ is displayed.

UPS xx KVA

SYSTEM NORMAL

system normal message

PRESS SIMULTANEOUSLY and keep pressed for 2 seconds

(The test is diabled if the BATTERY TEST selected is NONE)

UPS xx KVA

TESTING AUTONOMY

The battery starts to discharge completely thereby allowing the autonomy to be checked. Once the battery has been discharged, the test comes to an end automatically and the rectifier restarts.

To interrupt BATTERY autonomy Test, at any time: PRESS SIMULTANEOUSLY

 

and

keep pressed

 

for 2 seconds

 

 

 

10.9Resetting data loss manually

If the message »NOT CALIBRATED» appears on the main title page, this means that data (language and total number of mains failures) which do not directly affect the functioning of the machine have been lost. Despite this, data has still been lost and the intervention of a qualified technician is required.It is, nevertheless, possible to reset the normal operating mode by selecting the language desired as described under sect. 7.0.

MI00/10056 rev. 8 — 05/2006-- page 61

Image 61
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Emergency Procedure Electrical PrecautionsElectric Shock Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 36kVA Standard Configuration 24kVA Standard Configuration36kVA 480V/208V Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Fuse Access PlateCable EntryPoints Connection40.16 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Connection Uninterruptible Power System No Unauthorized Operation#$# % # #% + ,+% M10 AWGNest Stationary Tool Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations RAU Female FrontRear U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS2 QS1 QS4Terminal board compartment 40 --MI00/10056 rev -05/2006 Rear QS1 QS2 QS3 QS4 QS5Signal connections Emergency Power Off Controls Right Control Maintenance Bypass SHUT-DOWN Installing the EPOMimic Silencing Audible AlarmLiquid Crystal Display Inverter Alarms No Alarms Active RECT/BATT Alarms No Alarms ActiveLOAD/RES Alarms No Alarms Active Display Page HeadingsSelected Language English Battery Test WeeklyPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Inverter F xx.x Hz Xxx V B xxx V C xxx Vdc xxx V Ib xxxx aInverter F xx.x Hz AB xxx V BC xxx V CA xxx InverterLoad Main page Heading Alarms Message Condition Abnormal operating mode messagesSystem Alarm Overload Battery DischargingStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Matrix Power HistoryBattery Autonomy Test Battery TestResetting data loss manually System normal message11.1 AS400 11.2 RS232 Safety 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle EDP70 PLUS/24/18/12 Internal Battery Shelves13.4 EDP70 Plus above 24KVA Battery Cubicle 13.3 EDP70 Plus above 24KVA Battery Installation/Start-upEDP70 Plus System LOG