Garmin EDP70 manual Shut-Down, Installing the EPO

Page 46

9.0SHUT-DOWN

1.Close down the load in an orderly manner.

2. Push the

(inverter shutdown) button for more than 2 seconds.

3.Turn the main switch to OFF.

Note: If the electricity supply to the site is switched off outside normal working hours, the EDP70 PLUS should be shut down each evening, by either using the shutdown procedure or wiring in the Emergency Power Off (EPO) function, see figures 20, 23 or 26 (depending on the UPS size).

This will prevent the battery from discharging.

If, on the other hand, the supply to the site is continuous, the EDP70 PLUS should be operated 24 hours a day.

9.1Installing the EPO

To wire the EPO, open the link between terminal boards 1 and 2 and connect a signal switch, having the characteristics of an emergency button, closed under normal operating conditons and held open mechanically when operated: when the switch is enabled, the inverter and rectifier will stop, the battery relay will be opened and the load will be de-energized

To ensure that the EPO functions correctly, the signal should remain active for a period > 400 msec.

page 46 --MI00/10056 rev. 8 —05/2006

Image 46
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Electric Shock Electrical PrecautionsEmergency Procedure Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 36kVA Standard Configuration 24kVA Standard Configuration36kVA 480V/208V Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Cable Access PlateFuse Entry40.16 ConnectionPoints 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Uninterruptible Power System No Unauthorized Operation Connection#$# % # #% + ,+% Nest Stationary Tool AWGM10 Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations Rear FrontRAU Female U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS1 QS4 QS2Terminal board compartment 40 --MI00/10056 rev -05/2006 QS1 QS2 QS3 QS4 QS5 RearSignal connections Emergency Power Off Controls Right Control Maintenance Bypass Installing the EPO SHUT-DOWNMimic Silencing Audible AlarmLiquid Crystal Display LOAD/RES Alarms No Alarms Active RECT/BATT Alarms No Alarms ActiveInverter Alarms No Alarms Active Display Page HeadingsBattery Test Weekly Selected Language EnglishPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Inverter F xx.x Hz AB xxx V BC xxx V CA xxx Vdc xxx V Ib xxxx aInverter F xx.x Hz Xxx V B xxx V C xxx InverterLoad Main page Heading Alarms Message Condition Abnormal operating mode messagesSystem Alarm Overload Battery DischargingStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Power History MatrixResetting data loss manually Battery TestBattery Autonomy Test System normal message11.1 AS400 11.2 RS232 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up SafetyEDP70 PLUS/24/18/12 Internal Battery Shelves 13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle13.3 EDP70 Plus above 24KVA Battery Installation/Start-up 13.4 EDP70 Plus above 24KVA Battery CubicleEDP70 Plus System LOG