Garmin EDP70 manual Connection, Uninterruptible Power System No Unauthorized Operation

Page 30

5.0CONNECTION

Protection devices to be installed by the customer according to the information shown on page 23

 

L1

UTILITY

L2

INPUT

L3

 

N

Neutral not present on

50 and 80kVA ratings

 

U2

L1

 

 

V2

L2

OUTPUT

 

W2

L3

 

U

N

N

(Neutral separately derived

 

 

on 50 and 80kVA ratings)

V

 

 

 

 

 

W

 

 

 

N

 

EXTERNAL

 

 

 

 

BATTERIES

 

1

Remove link to connect remote E.P.O.

 

2

 

3

Battery Charge Inhibit

 

G

4

 

5

 

 

 

6

 

 

GROUND

Protection devices to be installed by the customer according to the information shown on page 23

L1 RESERVE L2

INPUT L3 N

UTILITY L1L2 INPUT L3

U1

V1

W1

N Neutral not

present on

50 and 80kVA

ratings

U

V

W

U2

L1

 

V2

L2

OUTPUT

W2

L3

 

N

N

(Neutral separately derived

 

 

on 50 and 80kVA ratings)

 

EXTERNAL

 

BATTERIES

G

GROUND

1

2

3

4

5

6

Remove link to connect remote E.P.O.

Battery Charge Inhibit

Figure 17 – Connection diagrams

THE AC AND DC SUPPLIES TO THE EDP70 PLUS UPS, AND THE AC OUTPUT FROM THE UPS, SHOULD BE FED THROUGH SUITABLY RATED CIRCUIT BREAKER OR FUSE(S) AND ISOLATING SWITCH SUITABLE FOR BRANCH CIRCUIT PROTECTION.

NOTE:

INTERRUPTING THE NEUTRAL FEED MAY CAUSE THE CHANGE IN GROUND-NEUTRAL VOLTAGE TO AFFECT

 

THE LOAD.

NOTE:

ALL CIRCUIT BREAKERS OR FUSES AND ISOLATING SWITCHES SHOULD BE FITTED AS CLOSE TO THE EDP70

 

PLUS UPS AS POSSIBLE AND MARKED WITH THE LABELS PROVIDED WITH THE UNIT.

 

IT IS ALSO RECOMMENDED A LABEL AS FOLLOWS

 

 

 

 

 

 

UNINTERRUPTIBLE POWER SYSTEM

 

 

 

NO UNAUTHORIZED OPERATION

 

 

 

 

 

page 30 --MI00/10056 rev. 8 —05/2006

Image 30
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Electric Shock Electrical PrecautionsEmergency Procedure Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 24kVA Standard Configuration 36kVA Standard Configuration36kVA 480V/208V Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Cable Access PlateFuse Entry40.16 ConnectionPoints 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Uninterruptible Power System No Unauthorized Operation Connection#$# % # #% + ,+% Nest Stationary Tool AWGM10 Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations Rear FrontRAU Female U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS1 QS4 QS2Terminal board compartment 40 --MI00/10056 rev -05/2006 QS1 QS2 QS3 QS4 QS5 RearSignal connections Emergency Power Off Controls Right Control Maintenance Bypass Installing the EPO SHUT-DOWNSilencing Audible Alarm MimicLiquid Crystal Display LOAD/RES Alarms No Alarms Active RECT/BATT Alarms No Alarms ActiveInverter Alarms No Alarms Active Display Page HeadingsBattery Test Weekly Selected Language EnglishPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Inverter F xx.x Hz AB xxx V BC xxx V CA xxx Vdc xxx V Ib xxxx aInverter F xx.x Hz Xxx V B xxx V C xxx InverterLoad Abnormal operating mode messages Main page Heading Alarms Message ConditionSystem Alarm Battery Discharging OverloadStop DUE to Overload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Power History MatrixResetting data loss manually Battery TestBattery Autonomy Test System normal message11.1 AS400 11.2 RS232 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up SafetyEDP70 PLUS/24/18/12 Internal Battery Shelves 13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle13.3 EDP70 Plus above 24KVA Battery Installation/Start-up 13.4 EDP70 Plus above 24KVA Battery CubicleEDP70 Plus System LOG