5.0CONNECTION
Protection devices to be installed by the customer according to the information shown on page 23
| L1 |
UTILITY | L2 |
INPUT | L3 |
| N |
Neutral not present on
50 and 80kVA ratings
| U2 | L1 |
|
| V2 | L2 | OUTPUT |
| W2 | L3 |
|
U | N | N | (Neutral separately derived |
|
| on 50 and 80kVA ratings) | |
V |
|
| |
|
|
| |
W |
|
|
|
N |
| EXTERNAL | |
|
| ||
|
| BATTERIES | |
| 1 | Remove link to connect remote E.P.O. | |
| 2 | ||
| 3 | Battery Charge Inhibit |
|
G | 4 |
| |
5 |
|
| |
| 6 |
|
|
GROUND
Protection devices to be installed by the customer according to the information shown on page 23
L1 RESERVE L2
INPUT L3 N
UTILITY L1L2 INPUT L3
U1 |
V1 |
W1 |
N Neutral not |
present on |
50 and 80kVA |
ratings |
U |
V |
W |
U2 | L1 |
|
V2 | L2 | OUTPUT |
W2 | L3 |
|
N | N | (Neutral separately derived |
|
| on 50 and 80kVA ratings) |
| EXTERNAL | |
| BATTERIES |
G
GROUND
1
2
3
4
5
6
Remove link to connect remote E.P.O.
Battery Charge Inhibit
Figure 17 – Connection diagrams
THE AC AND DC SUPPLIES TO THE EDP70 PLUS UPS, AND THE AC OUTPUT FROM THE UPS, SHOULD BE FED THROUGH SUITABLY RATED CIRCUIT BREAKER OR FUSE(S) AND ISOLATING SWITCH SUITABLE FOR BRANCH CIRCUIT PROTECTION.
NOTE: | INTERRUPTING THE NEUTRAL FEED MAY CAUSE THE CHANGE IN | ||
| THE LOAD. | ||
NOTE: | ALL CIRCUIT BREAKERS OR FUSES AND ISOLATING SWITCHES SHOULD BE FITTED AS CLOSE TO THE EDP70 | ||
| PLUS UPS AS POSSIBLE AND MARKED WITH THE LABELS PROVIDED WITH THE UNIT. | ||
| IT IS ALSO RECOMMENDED A LABEL AS FOLLOWS | ||
|
|
|
|
|
| UNINTERRUPTIBLE POWER SYSTEM |
|
|
| NO UNAUTHORIZED OPERATION |
|
|
|
|
|
page 30