4.2Installation

Check the rating label on the rear of the front panel of the EDP70 PLUS UPS to ensure the input/output voltages, frequency and load are all within the rating of the UPS.

EDP70 PLUS is designed to operate in an office environment with an optimum temperature of 68°F [20 C]. A gap of at least 4 in [ 10cm. ] must be maintained at rear of the UPS to ensure adequate ventilation. Nothing should be placed around the equipment which might restrict the airflow.

Ensure the interconnecting cables do not cause a hazard to the user.

A gap of at least 32 in [ 812 mm] must be maintained above the UPS to ensure adequate space for maintenance. The appropriate lifting equipment must be used to move the EDP70 PLUS UPS.

Figure 16 – UPS Ratings

 

 

 

 

UPS ratings

 

 

 

 

 

 

 

 

 

 

 

Description

U.M.

24

24

24

 

36

36

36

 

 

12kVA

18kVA

24kVA

 

24kVA

30kVA

36kVA

 

 

 

 

 

 

 

 

 

Output power

kVA

12

18

24

 

24

30

36

 

 

 

 

 

 

 

 

 

Nominal Load

kW

8

12

16

 

16

20

24

 

 

 

 

 

 

 

 

 

Maximum input power (with

 

 

 

 

 

 

 

 

unit @ nominal Load & battery

kVA

15

21

28

 

28

35

42

recharge)

 

 

 

 

 

 

 

 

Maximum dissipation (with

BTU/H

3750

5460

6800

 

7700

9500

11300

inverter @ nominal Load)

 

 

 

 

 

 

 

 

Number of battery cells

n

 

144

 

 

 

240

 

 

 

 

 

 

 

 

 

 

Battery voltage range

V

 

238-327

 

 

 

396-545

 

 

 

 

 

 

 

 

 

 

Battery

A

37

55

74

 

53

67

80

end-discharge current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS ratings

 

 

 

 

 

 

 

 

 

 

Description

U.M.

50

50

50

 

80

80

80

 

 

30kVA

40kVA

50kVA

 

50kVA

65kVA

80kVA

 

 

 

 

 

 

 

 

 

Output power

kVA

30

40

50

 

50

65

80

 

 

 

 

 

 

 

 

 

Nominal Load

kW

24

32

40

 

40

52

64

 

 

 

 

 

 

 

 

 

Maximum input power (with

 

 

 

 

 

 

 

 

unit @ nominal Load & battery

kVA

43

57

71

 

71

91

112

recharge)

 

 

 

 

 

 

 

 

Maximum dissipation (with

BTU/H

9300

11700

14300

 

14300

18600

22100

inverter @ nominal Load)

 

 

 

 

 

 

 

 

Number of battery cells

n

 

 

 

240

 

 

 

 

 

 

 

 

 

Battery voltage range

V

 

 

396-545

 

 

 

 

 

 

 

 

 

 

Battery

A

67

88

110

 

105

140

173

end-discharge current

 

 

 

 

 

 

 

 

page 26 --MI00/10056 rev. 8 —05/2006

Image 26
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Electric Shock Electrical PrecautionsEmergency Procedure Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 36kVA 480V/208V Configuration 24kVA Standard Configuration36kVA Standard Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Cable Access PlateFuse Entry40.16 ConnectionPoints 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Uninterruptible Power System No Unauthorized Operation Connection#$# % # #% + ,+% Nest Stationary Tool AWGM10 Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations Rear FrontRAU Female U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS1 QS4 QS2Terminal board compartment 40 --MI00/10056 rev -05/2006 QS1 QS2 QS3 QS4 QS5 RearSignal connections Emergency Power Off Controls Right Control Maintenance Bypass Installing the EPO SHUT-DOWNLiquid Crystal Display Silencing Audible AlarmMimic LOAD/RES Alarms No Alarms Active RECT/BATT Alarms No Alarms ActiveInverter Alarms No Alarms Active Display Page HeadingsBattery Test Weekly Selected Language EnglishPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Inverter F xx.x Hz AB xxx V BC xxx V CA xxx Vdc xxx V Ib xxxx aInverter F xx.x Hz Xxx V B xxx V C xxx InverterLoad System Alarm Abnormal operating mode messagesMain page Heading Alarms Message Condition Stop DUE to Overload Battery DischargingOverload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Power History MatrixResetting data loss manually Battery TestBattery Autonomy Test System normal message11.1 AS400 11.2 RS232 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up SafetyEDP70 PLUS/24/18/12 Internal Battery Shelves 13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle13.3 EDP70 Plus above 24KVA Battery Installation/Start-up 13.4 EDP70 Plus above 24KVA Battery CubicleEDP70 Plus System LOG