4.4Ventilation

UPS can work in a continuous environment within 18°F[-10°C] to 104°F [+40°C ] temperature range, although, ideally the ambient temperature should be below 78°F [25°C].

The heat, dissipated by the UPS (indicated on figure 7), is extracted by internal fans and then dissipated into the air.

The heat can be removed from the UPS room by a forced cooling ventilation system or, alternatively, an air conditioning system.

The required air changes per hour will depend on the UPS rating and this heat loss and on the cooling air temperature.

To calculate the required air flow for the dissipated power, the altitude and the cooling air temperature, the following equation can be used:

Pd

V= 2770 - - - - - - • e (0.125 h Tk / T0 )

 

 

 

Tr - Tk

with:

V =

air flow [mc/h]

 

Pd

= total dissipated power [kW]

 

Tr

=

max. temperature allowed into the room [104°F = 40°C = 313°K]

 

Tk

= Temperature of input cooling air

 

T0

=

273 °K

 

h

= altitude above the sea level [km]

MI00/10056 rev. 8 — 05/2006-- page 29

Image 29
Contents EDP70 Plus 2 --MI00/10056 rev -05/2006 Emergency Procedure Electrical PrecautionsElectric Shock Injuries Caused by Contact with Corrosive LiquidsContents Maintenance and Spare Parts Figures Equipment Delivery and Storage 8 -- MI00/10056 rev -05/2006 Introduction 36kVA 480V/208V Configuration 24kVA Standard Configuration36kVA Standard Configuration RECTIFIER/INVERTER 24/36kVA Ratings Contactor 24/36kVA Ratings Safety Eye goggles Rubber gloves Rubber apron Rubber boots Storage ALL Measurements are Millimeters and Inches 18 --MI00/10056 rev -05/2006 Cable Entry Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 24/36kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Battery Cabinet Drawing for 50/80kVA Ratings Fuse Access PlateCable EntryPoints Connection40.16 32.68BTU/H Recommended wire sizes UPS Type = 2770 - - - e 0.125 h Tk / T0 T k Connection Uninterruptible Power System No Unauthorized Operation#$# % # #% + ,+% M10 AWGNest Stationary Tool Indentor MoveableS2 = Equipment Reserve Switch Observe Polarities and Orientations RAU Female FrontRear U1V1W1N PE U V W N U2V2W2 N36 --MI00/10056 rev -05/2006 36 24/30/36kVA Connections QS2 QS1 QS4Terminal board compartment 40 --MI00/10056 rev -05/2006 Rear QS1 QS2 QS3 QS4 QS5Signal connections Emergency Power Off Controls Right Control Maintenance Bypass SHUT-DOWN Installing the EPOLiquid Crystal Display Silencing Audible AlarmMimic Inverter Alarms No Alarms Active RECT/BATT Alarms No Alarms ActiveLOAD/RES Alarms No Alarms Active Display Page HeadingsSelected Language English Battery Test WeeklyPower History Down to Access Load F xx.x Hz Xxx V B xxx V C Last Mains Failure xxd xxh xxm xxs Inverter F xx.x Hz Xxx V B xxx V C xxx Vdc xxx V Ib xxxx aInverter F xx.x Hz AB xxx V BC xxx V CA xxx InverterLoad System Alarm Abnormal operating mode messagesMain page Heading Alarms Message Condition Stop DUE to Overload Battery DischargingOverload RECTIFIER/BATTERY Alarms Message Condition Inverter Alarms Message Condition LOAD/RESERVE Alarms Message Condition Power History Matrix Power HistoryBattery Autonomy Test Battery TestResetting data loss manually System normal message11.1 AS400 11.2 RS232 Safety 13.1 EDP70 PLUS/24/18/12 Battery Installation/Start-up13.2 EDP70 PLUS/24/18/12 Optional Battery Cubicle EDP70 PLUS/24/18/12 Internal Battery Shelves13.4 EDP70 Plus above 24KVA Battery Cubicle 13.3 EDP70 Plus above 24KVA Battery Installation/Start-upEDP70 Plus System LOG