Appendix E MODBUS Commands | Series |
|
|
Appendix E Modbus Communication
Applicable Flow Meter Models
Sierra
Overview
This document describes the preliminary implementation of the Modbus communication protocol for use in monitoring common process variables in the Sierra
Reference Documents
The following documents are available online from www.modbus.org.
Modbus Application Protocol Specification V1.1
Modbus Over Serial Line Specification & Implementation Guide V1.0
Modicon Modbus Protocol Reference Guide
Menu Items
The following menu items are in the Output Menu and allow selection and control of the Modbus communication protocol.
Address
When the Modbus protocol is selected, the Modbus address is equal to the user program- mable device address if it is in the range 1…247, in accordance with the Modbus specifica- tion. If the device address is zero or is greater than 247, then the Modbus address is inter- nally set to 1.
Comm Protocol
The Comm Protocol menu allows selection of “Modbus RTU Even,” “Modbus RTU Odd,” or “Mod- bus RTU None2,” or “Modbus RTU None1,”
When changing the protocol, the change is made as soon as the Enter key is pressed.
|