Sierra 240-VTP, 241-VTP Appendix E Modbus Communication, Applicable Flow Meter Models

Page 83

Appendix E MODBUS Commands

Series 24-HP Instruction Manual

 

 

Appendix E Modbus Communication

Applicable Flow Meter Models

Sierra Innova-Mass® Mass Flow Meters, Models 240 and 241 with Modbus communication pro- tocol and firmware version 3.00.02 and above.

Overview

This document describes the preliminary implementation of the Modbus communication protocol for use in monitoring common process variables in the Sierra Innova-Mass® Vortex flow meter. The physical layer utilizes the half-duplex RS-485 port, and the Modbus protocol.

Reference Documents

The following documents are available online from www.modbus.org.

Modbus Application Protocol Specification V1.1

Modbus Over Serial Line Specification & Implementation Guide V1.0

Modicon Modbus Protocol Reference Guide PI–MBUS–300 Rev. J

Menu Items

The following menu items are in the Output Menu and allow selection and control of the Modbus communication protocol.

Address

When the Modbus protocol is selected, the Modbus address is equal to the user program- mable device address if it is in the range 1…247, in accordance with the Modbus specifica- tion. If the device address is zero or is greater than 247, then the Modbus address is inter- nally set to 1.

Comm Protocol

The Comm Protocol menu allows selection of “Modbus RTU Even,” “Modbus RTU Odd,” or “Mod- bus RTU None2,” or “Modbus RTU None1,” (non-standard Modbus) with Even, Odd and None re- ferring to the parity selection. When even or odd parity is selected, the unit is configured for 8 data bits, 1 parity bit and 1 stop bit; with no parity, the number of stop bits is 1 (non-standard) or 2.

When changing the protocol, the change is made as soon as the Enter key is pressed.

IM-24-HP

E-1

Image 83
Contents Models 240-VT, 240-VTP, 241-VT, 241-VTP Copyright Sierra Instruments Customer NoticeTable of Contents Troubleshooting and Repair Tables FiguresTable of Contents Innova-MassMulti-Parameter Vortex Mass Flow Meters Using This ManualIntroduction Technical Assistance Receipt of System ComponentsVelocity Measurement How the Innova-Mass Vortex Mass Flow Meter OperatesVortex Frequency Sensing Vortex Shedding FrequencyGas Liquid Flow Velocity RangeReynolds Number Range for the Innova-Mass Temperature MeasurementPressure Measurement Flow Meter ConfigurationsFlow Meter Electronics Flow Meter Installation Requirements InstallationInstallation Overview Unobstructed Flow Requirements Flange Bolt Specifications Series 240 In-Line Flow Meter InstallationWafer-Style Flow Meter Installation Wafer-Style Flow Meter InstallationFlange-Style Flow Meter Installation Flange-Style Flow Meter InstallationIsolation Valve Selection Series 241 Insertion Flow Meter InstallationMounting Position Cold Tap Guidelines Flow Hot Tap GuidelinesUse the Correct Insertion Formula Flow Meter InsertionExample Installing Flow Meters with a Compression ConnectionInsertion Procedure for Meters with a Compression Connection Example 2 NPT Style Meters Installing Flow Meters with a Packing Gland ConnectionExample 1 Flange Style Meters Flow Meter with Permanent Insertion Tool 10. Flow Meter with Removable Insertion Tool 11. Insertion Calculation Meters without Insertion Tool Installation Display/Keypad Adjustment All Meters Adjusting Meter Orientation13. Enclosure Viewing Adjustment Enclosure Adjustment Series 240 OnlyDC Power Wiring Wiring ConnectionsInput Power Connections AC Power Wiring16. Load Resistance Versus Input Voltage MA Output ConnectionsPulse Output Connections 20. Isolated Pulse Output with External Power Supply 23. Isolated Alarm Output with External Power Supply Alarm Output Connections25. Isolated Alarm Output Using Meter Provided Power Supply Remote Electronics WiringOptional Energy EMS Input Electronics Wiring Optional Input Electronics WiringPage Sierra Operating InstructionsFlow Meter Display/Keypad Start-Up Run Mode ScreensProgramming the Flow Meter Using the Setup MenusTimeConstSec Xxxx Output MenuFirst, set the desired units of measurement Example for Setting an OutputDisplay Menu Example for Changing a Run Mode Display ItemExample for Setting an Alarm Alarms MenuTotalizer #1 Menu Example for Setting the TotalizerTotalizer #2 Menu Energy Menu For EMS Energy Meters Only ConfigurationFluid Menu Units Menu Time & Date Menu Example for Setting the TimeDiagnostics Menu Calibration Menu Password Menu Hidden Diagnostics Menus Troubleshooting and RepairColumn One Hidden Diagnostics Values IM-24-HP A2D Ref. Resistor = Factory Use Only Analog Output Calibration Troubleshooting the Flow Meter Symptom Output at no Flow Symptom No Output Symptom Meter Displays Temperature Fault Electronics Assembly Replacement All Meters Pressure Sensor Replacement Appendix a Product Specifications Appendix a Specifications Appendix a Specifications Cnpt IP66, Nema Page C D Appendix B GlossaryK L S T Page Viscosity Appendix C Fluid CalculationsCalculations for Steam T & P DensityDensity for real gases is calculated from the equation Calculations for Gas Real Gas and Other GasCalculations for Liquid Page PV AO Appendix D Hart Commands with DD MenuPV AO PV LRV URV Appendix D Hart Commands without DD MenuApplicable Flow Meter Models Appendix E Modbus CommunicationModbus Order Register Definitions Appendix E Modbus Commands Following registers contain the display units strings Control Register Definitions Examples An attempt to read registers that don’t exist 8C 3A CRC not the correct CRC EJS-02-06-07 Appendix E Modbus Commands