Sierra 240-VTP, 241-VTP instruction manual Following registers contain the display units strings

Page 87

Series 24-HP Instruction Manual

Appendix E MODBUS Commands

 

 

The following registers contain the display units strings:

Registers

32007-32012

32001-32006

32025-32030

32019-32024

32031-32036

32013-32017

Variable

Volume flow units Mass flow units Temperature units Pressure units

Density units Energy flow units

Data type

Units

Function code

string

03, 04

 

 

 

string

03, 04

string

03, 04

string

 

03, 04

string

03, 04

string

03, 04

Addresses 2006-2011 2000-2005 2024-2029 2018-2023

2030-2035

2012-2017

Function codes 03 (read holding registers) and 04 (read input regis- ters) are the only codes supported for reading these registers, and function codes for writing holding registers are not implemented. We recommend that the floating point and long integer registers be read in a single operation with the number of registers being a mul- tiple of two. If these data are read in two separate operations, each reading a single 16-bit register, then the value will likely be invalid.

The floating point registers with values in display units are scaled to the same units as are displayed, but are instantaneous values that are not smoothed. If display smoothing is enabled (non-zero value entered in the Display TC item in the Display Menu), then the register values will not agree exactly with the displayed val- ues.

Exception Status Definitions

The Read Exception Status command (function code 07) returns the exception status byte, which is defined as follows. This byte may be cleared by setting “coil” register #00003 (function code 5, address 2, data = 0xff00).

Bit(s)

Definition

0-1

Byte order (see Modbus Order on page 2)

 

0 = 3-2:1-0 1 = 2-3:0-1

 

2 = 1-0:3-2 3 = 0-1:2-3

2Temperature sensor fault

3 Pressure sensor fault

4 A/D converter fault

5 Period overflow

6 Pulse overflow

7 Configuration changed

IM-24-HP

E-5

Image 87
Contents Models 240-VT, 240-VTP, 241-VT, 241-VTP Copyright Sierra Instruments Customer NoticeTable of Contents Troubleshooting and Repair Tables FiguresTable of Contents Using This Manual IntroductionInnova-MassMulti-Parameter Vortex Mass Flow Meters Technical Assistance Receipt of System ComponentsVelocity Measurement How the Innova-Mass Vortex Mass Flow Meter OperatesVortex Frequency Sensing Vortex Shedding FrequencyGas Liquid Flow Velocity RangeReynolds Number Range for the Innova-Mass Temperature MeasurementPressure Measurement Flow Meter ConfigurationsFlow Meter Electronics Installation Installation OverviewFlow Meter Installation Requirements Unobstructed Flow Requirements Flange Bolt Specifications Series 240 In-Line Flow Meter InstallationWafer-Style Flow Meter Installation Wafer-Style Flow Meter InstallationFlange-Style Flow Meter Installation Flange-Style Flow Meter InstallationSeries 241 Insertion Flow Meter Installation Mounting PositionIsolation Valve Selection Cold Tap Guidelines Flow Hot Tap GuidelinesUse the Correct Insertion Formula Flow Meter InsertionExample Installing Flow Meters with a Compression ConnectionInsertion Procedure for Meters with a Compression Connection Installing Flow Meters with a Packing Gland Connection Example 1 Flange Style MetersExample 2 NPT Style Meters Flow Meter with Permanent Insertion Tool 10. Flow Meter with Removable Insertion Tool 11. Insertion Calculation Meters without Insertion Tool Installation Display/Keypad Adjustment All Meters Adjusting Meter Orientation13. Enclosure Viewing Adjustment Enclosure Adjustment Series 240 OnlyDC Power Wiring Wiring ConnectionsInput Power Connections AC Power Wiring16. Load Resistance Versus Input Voltage MA Output ConnectionsPulse Output Connections 20. Isolated Pulse Output with External Power Supply 23. Isolated Alarm Output with External Power Supply Alarm Output Connections25. Isolated Alarm Output Using Meter Provided Power Supply Remote Electronics WiringOptional Energy EMS Input Electronics Wiring Optional Input Electronics WiringPage Operating Instructions Flow Meter Display/KeypadSierra Start-Up Run Mode ScreensProgramming the Flow Meter Using the Setup MenusTimeConstSec Xxxx Output MenuFirst, set the desired units of measurement Example for Setting an OutputDisplay Menu Example for Changing a Run Mode Display ItemExample for Setting an Alarm Alarms MenuTotalizer #1 Menu Example for Setting the TotalizerTotalizer #2 Menu Energy Menu For EMS Energy Meters Only ConfigurationFluid Menu Units Menu Time & Date Menu Example for Setting the TimeDiagnostics Menu Calibration Menu Password Menu Hidden Diagnostics Menus Troubleshooting and RepairColumn One Hidden Diagnostics Values IM-24-HP A2D Ref. Resistor = Factory Use Only Analog Output Calibration Troubleshooting the Flow Meter Symptom Output at no Flow Symptom No Output Symptom Meter Displays Temperature Fault Electronics Assembly Replacement All Meters Pressure Sensor Replacement Appendix a Product Specifications Appendix a Specifications Appendix a Specifications Cnpt IP66, Nema Page C D Appendix B GlossaryK L S T Page Viscosity Appendix C Fluid CalculationsCalculations for Steam T & P DensityDensity for real gases is calculated from the equation Calculations for Gas Real Gas and Other GasCalculations for Liquid Page PV AO Appendix D Hart Commands with DD MenuPV AO PV LRV URV Appendix D Hart Commands without DD MenuApplicable Flow Meter Models Appendix E Modbus CommunicationModbus Order Register Definitions Appendix E Modbus Commands Following registers contain the display units strings Control Register Definitions Examples An attempt to read registers that don’t exist 8C 3A CRC not the correct CRC EJS-02-06-07 Appendix E Modbus Commands