SMC Networks 1560 user manual At this time

Page 24

Chapter 4 — Programming Considerations

Modbus

Name

Values

 

Description

Address

 

 

 

 

 

 

 

 

 

40033

MBP Status

0

This register is used to

 

 

to

communicate the last Invalid

 

 

3

MBP Status value. Possible

 

 

 

values are as follows:

 

 

 

0 No error since power

 

 

 

 

cycle

 

 

 

1

Invalid Global Cmd

 

 

 

 

Request Most likely the

 

 

 

 

slave address for the

 

 

 

 

MBP is > 16 and is

 

 

 

 

configured for Global

 

 

 

 

Cmd

 

 

 

2

Invalid Global Length

 

 

 

 

The host is not configured

 

 

 

 

to send enough Global

 

 

 

 

Data to support this

 

 

 

 

node’s Modbus Plus

 

 

 

 

address

 

 

 

3

Invalid Write Range

 

 

 

 

An MSTR Type 1 write

 

 

 

 

cmd was received

 

 

 

 

attemtpting to write into

 

 

 

 

the 40011 to 40100

 

 

 

 

address range. The cmd

 

 

 

 

was disregarded by the

 

 

 

 

MBP with a successful

 

 

 

 

response returned to the

 

 

 

 

host.

Note that this register is only cleared on power up, and will only be updated when a new error condition arises. Therefore be aware that a non-zero value will stay in the register after an initial error condition until the next power cycle.

40034

Not Defined

Reserved for future use

to

at this time

 

40100

 

 

24

Image 24
Contents 1560 Table of Contents Please Read This Notice Quick Start Guide Step-by-StepRevisions Product Specifications Modbus Plus SpecificationsGeneral Specifications Configuration via dip switches Slave Address Host Address24 VDC Operating Temp To 50 C Storage Temp 40 to 85 C Supported Mstr Programming Commands Modbus Plus Port FunctionalityModbus Plus Communications Modbus Register Map Mstr Type 5 Write Global DataMBP Modbus Address Space Hardware Setup 1560-MBP Card Setup Connecting Power to the 1560-MBP CardDip Switch Configuration Switch SW Function Description Details Fault on LossModbus PlusSwitch SW 2 cont’d Contents Writing to the 1560-MBP Global Data Enabled Mstr Type Programming Considerations1560-MBP Global Data Enable 40400 Active Abort Error 40410Modicon Programming Example Mstr SuccessHost Issued Write Commands Mstr Type Reading from the 1560-MBP Global Data Mstr TypeModicon Programming Example Mstr Type Host Issued Read Commands Mstr Type Enable 40500 Active40510 0001040050 4006000020 MBP Status Registers 40021 to Modbus Name Values Description AddressBatch At this time Troubleshooting LED Troubleshooting TableLED Locations SCANport Mbpstat Diagnostics Cable Diagram TxRxD+Technical Support Technical Support ContactsAppendix a MBP Modbus Register MapMBP Modbus Appendix B Device Specific HintsSetting up the Adaptor I/O Data Logic Control Word Bit Function DescriptionDrive Status Word Bit Function Description Hardware Configuration Appendix CSingle Drive Peer Cop Application Example OverviewSwitch Position Description Configuration Extension BlocksPLC REF Drive Status Ladder Logic Programming RefOffset DescriptionPLC Ref PLC Name Description Special Precautions and hints TimingAddressing HintsAppendix D Mounting and SCANport Cabling InstructionsMounting Instructions 70mmCable Requirements Appendix E SCANport Datalink OperationRepair and Warranty Service and RepairGeneral Warranty Policy Hardware Product Warranty Details Limitation of LiabilityContents