Appendix B — Device Specific Hints

Appendix B

Device Specific Hints

SMC Dialogue Plus

The SMC Dialogue Plus does not support Datalinks, therefore the configuration of SW1-7 and 8 should not include any of the Datalinks Enabled. If a Datalink is enabled, the SCANport Status LED will toggle, indicating an error in the SCANport communications.

The version of SMC which was tested (Rev 1.05) had 88 parameters. Each parameter was accessible in the Modbus register listing shown in Appendix A. Note that if one of the 88 parameters is to be changed from a host that the host must enable the EEPROM Storage function by writing a 2 into the Parameter Management parameter (Parameter 17 - Modbus address 40117 ).

SMP 3

The SMP3 does not support Datalinks, therefore the configuration of Datalinks should not include any of the Datalinks Enabled. If a Datalink is enabled, the SCANport Status LED will toggle, indicating an error in the SCANport communications.

The 1560-MBP is able to read all of the parameters out of the SMP3 unit.

Variable Speed Drives

In order to enable Frequency control from the 1560-MBP, the drive parameter FREQUENCY SELECT 2 must be configured for the appropriate Adapter ID representing the 1560-MBP module. This will normally be Adaptor #2, unless a SCANport expander is being used (in which case this Adaptor number will be based on the port the 1560-MBP is plugged into).

Setting up the Adaptor I/O - Datalinks Out

Selects the parameter values which will be made available from the 1560-MBP via Global Data Out. Placement of the values in the 1560-MBP is referenced in Appendix A.

Data Out

Suggested

 

Image

Parameter

Description

A1

54

Output Current

A2

1

Output Volts

B1

23

Output Power

B2

53

DC Bus Voltage

31

Image 31
Contents 1560 Table of Contents Please Read This Notice Step-by-Step Quick Start GuideRevisions Configuration via dip switches Slave Address Host Address Product SpecificationsModbus Plus Specifications General Specifications24 VDC Operating Temp To 50 C Storage Temp 40 to 85 C Modbus Plus Port Functionality Supported Mstr Programming CommandsModbus Plus Communications Mstr Type 5 Write Global Data Modbus Register MapMBP Modbus Address Space 1560-MBP Card Setup Connecting Power to the 1560-MBP Card Hardware SetupDip Switch Configuration Switch SW Plus Function Description Details Fault onLoss ModbusSwitch SW 2 cont’d Contents Programming Considerations Writing to the 1560-MBP Global Data Enabled Mstr Type1560-MBP Global Data Success Enable 40400 ActiveAbort Error 40410 Modicon Programming Example MstrHost Issued Write Commands Mstr Type Global Data Mstr Type Reading from the 1560-MBPModicon Programming Example Mstr Type 00010 Host Issued Read Commands Mstr TypeEnable 40500 Active 4051040060 4005000020 Modbus Name Values Description Address MBP Status Registers 40021 toBatch At this time LED Troubleshooting Table TroubleshootingLED Locations SCANport Mbpstat Diagnostics TxRxD+ Cable DiagramTechnical Support Contacts Technical SupportMBP Modbus Register Map Appendix aMBP Modbus Device Specific Hints Appendix BLogic Control Word Bit Function Description Setting up the Adaptor I/O DataDrive Status Word Bit Function Description Overview Hardware ConfigurationAppendix C Single Drive Peer Cop Application ExampleConfiguration Extension Blocks Switch Position DescriptionPLC REF Drive Status RefOffset Description Ladder Logic ProgrammingPLC Ref PLC Name Description Timing Special Precautions and hintsHints Addressing70mm Appendix DMounting and SCANport Cabling Instructions Mounting InstructionsCable Requirements SCANport Datalink Operation Appendix EService and Repair Repair and WarrantyGeneral Warranty Policy Limitation of Liability Hardware Product Warranty DetailsContents