Appendix C — Peer Cop Example

Appendix C

Single Drive Peer Cop Application Example

Overview

This example shows how to configure a PLC to control and monitor a single drive using Peer Cop. Note that this example may easily be extended to 16 drives on one network. Additional sets of 16 drives may be controlled by adding Modbus Plus Network Option Modules to the PLC.

In this example, a 984-785E is connected to a 1560-MBP controlling a 1336Plus drive. It is strongly suggested that the user initially follow this application closely and then modify the application to suit his requirements. This should minimize the effort required to get your implementation up and running.

Hardware Configuration

In this application, we have made the following assumptions:

984 Processor Node Address

7

1560-MBP Configuration

 

Node Address

6

Data Links Enabled

A, B, C, D

Global Control

Enabled

Comm Loss Fault

Disabled

The 1560-MBP Dip Switch 1 Configuration is as follows:

Switch

Position

Description

1

Off

Set the Global Data Host PLC to Node 7

2

On

This tells the 1560-MBP which PLC is

3

On

controlling the drive

4

Off

 

5

Off

 

6

Off

 

 

 

 

7

On

Enable Datalinks A, B,C,D

8

On

 

 

 

 

33

Image 33
Contents 1560 Table of Contents Please Read This Notice Step-by-Step Quick Start GuideRevisions Modbus Plus Specifications Product SpecificationsGeneral Specifications Configuration via dip switches Slave Address Host Address24 VDC Operating Temp To 50 C Storage Temp 40 to 85 C Supported Mstr Programming Commands Modbus Plus Port FunctionalityModbus Plus Communications Modbus Register Map Mstr Type 5 Write Global DataMBP Modbus Address Space Hardware Setup 1560-MBP Card Setup Connecting Power to the 1560-MBP CardDip Switch Configuration Switch SW Loss Function Description Details Fault onModbus PlusSwitch SW 2 cont’d Contents Programming Considerations Writing to the 1560-MBP Global Data Enabled Mstr Type1560-MBP Global Data Abort Error 40410 Enable 40400 ActiveModicon Programming Example Mstr SuccessHost Issued Write Commands Mstr Type Reading from the 1560-MBP Global Data Mstr TypeModicon Programming Example Mstr Type Enable 40500 Active Host Issued Read Commands Mstr Type40510 0001040050 4006000020 Modbus Name Values Description Address MBP Status Registers 40021 toBatch At this time Troubleshooting LED Troubleshooting TableLED Locations SCANport Mbpstat Diagnostics TxRxD+ Cable DiagramTechnical Support Contacts Technical SupportAppendix a MBP Modbus Register MapMBP Modbus Device Specific Hints Appendix BSetting up the Adaptor I/O Data Logic Control Word Bit Function DescriptionDrive Status Word Bit Function Description Appendix C Hardware ConfigurationSingle Drive Peer Cop Application Example OverviewConfiguration Extension Blocks Switch Position DescriptionPLC REF Drive Status Ladder Logic Programming RefOffset DescriptionPLC Ref PLC Name Description Timing Special Precautions and hintsHints AddressingMounting and SCANport Cabling Instructions Appendix DMounting Instructions 70mmCable Requirements SCANport Datalink Operation Appendix ERepair and Warranty Service and RepairGeneral Warranty Policy Limitation of Liability Hardware Product Warranty DetailsContents