Chapter 5 — Troubleshooting

NAME

Color

Status

Indication

 

 

 

 

 

 

Two Flashes

The node is hearing the token being

 

 

then OFF for

passed among other nodes, but is

 

 

two seconds

never receiving the token. Check the

 

 

 

network for an open circuit or defective

 

 

 

termination.

 

 

 

 

 

 

Three Flashes

The node is not hearing any other

 

 

then OFF for

nodes. It is periodically claiming the

 

 

1.7 seconds

token but finding no other node to

 

 

 

which to pass it. Check the network for

 

 

 

an open circuit or defective termination.

 

 

 

 

 

 

Four Flashes

The node has heard a valid message

 

 

then OFF for

from another node that is using the

 

 

1.4 seconds

same address as this node. The node

 

 

 

remains in this state as long as it

 

 

 

continues to hear the duplicate address.

 

 

 

If the duplicate address is not heard for

 

 

 

five seconds, the node then changes to

 

 

 

the pattern of one flash every second.

 

 

 

 

 

 

 

 

SCANport

Green

Steady

SCANport connection if OK

Status

 

 

 

 

Blinking

Check cable connections. Indicates that

 

 

 

 

 

the 1560-MBP unit is not able to link up

 

 

 

with the drive’s SCANport. Make sure

 

 

 

that the A-B device supports Datalinks if

 

 

 

the 1560-MBP Datalinks are enabled.

 

 

 

 

 

Red

Steady

The SCANport connection has faulted.

 

 

 

Check configuration switch settings,

 

 

 

SCANport cable connections, cycle

 

 

 

power. Contact ProSoft factory support

 

 

 

if problem persists.

 

 

 

 

26

Image 26
Contents 1560 Table of Contents Please Read This Notice Quick Start Guide Step-by-StepRevisions General Specifications Product SpecificationsModbus Plus Specifications Configuration via dip switches Slave Address Host Address24 VDC Operating Temp To 50 C Storage Temp 40 to 85 C Modbus Plus Communications Supported Mstr Programming CommandsModbus Plus Port Functionality MBP Modbus Address Space Modbus Register MapMstr Type 5 Write Global Data Dip Switch Configuration Hardware Setup1560-MBP Card Setup Connecting Power to the 1560-MBP Card Switch SW Modbus Function Description Details Fault onLoss PlusSwitch SW 2 cont’d Contents Writing to the 1560-MBP Global Data Enabled Mstr Type Programming Considerations1560-MBP Global Data Modicon Programming Example Mstr Enable 40400 ActiveAbort Error 40410 SuccessHost Issued Write Commands Mstr Type Modicon Programming Example Mstr Type Reading from the 1560-MBPGlobal Data Mstr Type 40510 Host Issued Read Commands Mstr TypeEnable 40500 Active 0001000020 4005040060 MBP Status Registers 40021 to Modbus Name Values Description AddressBatch At this time LED Locations TroubleshootingLED Troubleshooting Table SCANport Mbpstat Diagnostics Cable Diagram TxRxD+Technical Support Technical Support ContactsMBP Modbus Appendix aMBP Modbus Register Map Appendix B Device Specific HintsDrive Status Word Bit Function Description Setting up the Adaptor I/O DataLogic Control Word Bit Function Description Single Drive Peer Cop Application Example Hardware ConfigurationAppendix C OverviewSwitch Position Description Configuration Extension BlocksPLC REF Drive Status PLC Ref PLC Name Description Ladder Logic ProgrammingRefOffset Description Special Precautions and hints TimingAddressing HintsMounting Instructions Appendix DMounting and SCANport Cabling Instructions 70mmCable Requirements Appendix E SCANport Datalink OperationGeneral Warranty Policy Repair and WarrantyService and Repair Hardware Product Warranty Details Limitation of LiabilityContents