SMC Networks 1560 Setting up the Adaptor I/O Data, Logic Control Word Bit Function Description

Page 32

Appendix B — Device Specific Hints

C1

 

 

 

C2

 

 

 

D1

19

Maximum Frequency

 

D2

4

Last fault

Setting up the Adaptor I/O - Data In

Selects the parameters which will be made accessible for configuration/ writing from the 1560-MBP. As with the Data Out parameters, there are eight possible selections. These may be chosen by the programmer to meet the needs of the application.

Logic Control Word

Since the most common implementation of the 1560-MBP is with the variable speed drives, we have included the following table for the more commonly used control bits. This word should be verified in the A-B User Manual for the particular device being controlled.

Bit

Function

Description

0

Stop

1

= Stop, 0 = Not Stop

1

Start

1

= Start, 0 = Not Start

2

Jog

1

= Jog, 0 = Not Jog

3

Clear Faults

1

= Clear, 0 = Not Clear

4, 5

Direction

00

= No Command

 

 

01

= Forward

 

 

10

= Reverse

 

 

11

= Hold Direction

Drive Status Word

Since the most common implementation of the 1560-MBP is with the variable speed drives, we have included the following table for the more commonly used Status bits. This word should be verified in the A-B User Manual for the particular device being monitored.

Bit

Function

Description

0

Enabled

1

= Enabled

1

Running

1

= Running

2

Cmd Direction

1

= Forward, 0 = Reverse

3

Actual Direction

1

= Forward, 0 = Reverse

4

Accel

1 = Accelerating

5

Decel

1

= Decellerating

6

Alarm

1 = Alarm Active

7

Fault

1 = Fault Active

8

At Speed

1 = At Speed

32

Image 32
Contents 1560 Table of Contents Please Read This Notice Quick Start Guide Step-by-StepRevisions Product Specifications Modbus Plus SpecificationsGeneral Specifications Configuration via dip switches Slave Address Host Address24 VDC Operating Temp To 50 C Storage Temp 40 to 85 C Modbus Plus Communications Supported Mstr Programming CommandsModbus Plus Port Functionality MBP Modbus Address Space Modbus Register MapMstr Type 5 Write Global Data Dip Switch Configuration Hardware Setup1560-MBP Card Setup Connecting Power to the 1560-MBP Card Switch SW Function Description Details Fault on LossModbus PlusSwitch SW 2 cont’d Contents Writing to the 1560-MBP Global Data Enabled Mstr Type Programming Considerations1560-MBP Global Data Enable 40400 Active Abort Error 40410Modicon Programming Example Mstr SuccessHost Issued Write Commands Mstr Type Modicon Programming Example Mstr Type Reading from the 1560-MBPGlobal Data Mstr Type Host Issued Read Commands Mstr Type Enable 40500 Active40510 0001000020 4005040060 MBP Status Registers 40021 to Modbus Name Values Description AddressBatch At this time LED Locations TroubleshootingLED Troubleshooting Table SCANport Mbpstat Diagnostics Cable Diagram TxRxD+Technical Support Technical Support ContactsMBP Modbus Appendix aMBP Modbus Register Map Appendix B Device Specific HintsDrive Status Word Bit Function Description Setting up the Adaptor I/O DataLogic Control Word Bit Function Description Hardware Configuration Appendix CSingle Drive Peer Cop Application Example OverviewSwitch Position Description Configuration Extension BlocksPLC REF Drive Status PLC Ref PLC Name Description Ladder Logic ProgrammingRefOffset Description Special Precautions and hints TimingAddressing HintsAppendix D Mounting and SCANport Cabling InstructionsMounting Instructions 70mmCable Requirements Appendix E SCANport Datalink OperationGeneral Warranty Policy Repair and WarrantyService and Repair Hardware Product Warranty Details Limitation of LiabilityContents