Line Service Commands
<IP_address>
Specify the IP address of the remote host that is receiving the vmodem connection.
<TCP_port>
Specify the TCP port that the remote host is lisening on for the vmodem connection.
delete
Deletes the specified entry from the phone number table.
Set Modbus-Slave Line
Description | Sets the Modbus slave parameters for the line. |
User Level | Admin |
Syntax | set |
| [protocol rtuascii] |
Options | crlf |
| When Modbus/ASCII is selected, adds a CR/LF to the end of the transmission; most |
| Modbus devices require this option. The default is On. |
| protocol |
| Specify the protocol that is used between the Modbus Master(s) and Modbus Slave(s), |
| either RTU or ASCII. |
|
|
| You can specify a range of UIDs |
| comma delimited; for example, |
Set Modbus-Master Line
Description | Sets the Modbus master parameters for the line. |
User Level | Admin |
Syntax | set |
| [protocol rtuascii] |
| [[entry <number> [port <port>] [protocol udptcp] |
| |
|
Options crlf
When Modbus/ASCII is selected, adds a CR/LF to the end of the transmission; most
Modbus devices require this option. The default is On.
protocol
Specify the protocol that is used between the Modbus Master(s) and Modbus Slave(s), either RTU or ASCII.
entry
You can specify up to 16 Modbus Slave Remote IP Mapping entries (the UIDs must not overlap).
port
The destination port of the remote Modbus TCP Slave that the IOLAN will connect to.
53